6. Operational modes
6.1. Panic function mode with separated fault outputs
Software requirement, fog cannon: Software version 2.50 or higher.
Software requirement, MultiCard: Software version 1.02 or higher.
Device requirement: This program will run on any type of PROTECT Fog Cannon.
Dipswitch settings:
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
0
Terminal “V+” is currently not used, and should be left unconnected.
For the Panic Release function to work, the following conditions must be met:
•
The Disable input on the fog cannon’ mainboard must be inactive
- Use the Disable input on the MultiCard instead, since this input will not influence the Panic signal
•
The Fire Alarm input on the fog cannon’ mainboard must be inactive
- The Fire Alarm input IS DESIGNED TO STOP AND BLOCK ALL FOG immediately
- This is a mandatory function demanded by national and local fire authorities, when used in premises
monitored by fire alarm systems, and hence may not and cannot be overruled
- If service disable functionality is requested, for servicing attached alarm system, please use the
SS input on the MultiCard instead. It was designed specifically with this purpose in mind
•
Dipswitch 9 on the fog cannon’ mainboard must be set to ON, to enable Panic functionality
This input is fixed “normally open” (activates when voltage is applied).
Outputs 2 to 9 signal various fault conditions on separate outputs.
See list above.
Do NOT rely solely on the fault indicating outputs on the MultiCard.
Fault, Fluid and Fog outputs on fog cannon mainboard should still be monitored for activity.
Inputs functionality:
IN-SS
Activates “Blocking mode” when connected to gnd on mainboard
IN-2
Panic button
IN-3
Disable (this Disable input allows Panic to work. Will not turn off heat)
IN-4
No function
Outputs functionality:
OUT-1
Panic release active
OUT-2
E1_MAINS_VOLTAGE_LOST
OUT-3
E3_FIRE_ALARM_ACTIVE or E16_PANNIC_NOT_RELEASED
OUT-4
E4_BATTERY_VOLTAGE_LOW or E5_BAT_CHARGE_TIMEOUT or E6_BAT_LOADTEST_FAIL
OUT-5
E7_BOARD_TEMP_HIGH or E8_BOARD_TEMP_LOW or E14_BAT_TEST_CIRC_FAIL
OUT-6
E9_TEMP_TERM_HIGH
OUT-7
E10_TEMP_TERM_LOW
OUT-8
E12_PUMP_TIMEOUT
OUT-9
E13_AUX_12V_OVERLOAD