81
Manual & Installer Guide
Residential & Commercial Heat Pump with
‘O’ Reversing Valve
5 Wire, 1 Stage Cooling, 1 Stage Heat
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
Y1 1st Stage Compressor
(Cool or Heat)
G Fan
Residential & Commercial Heat Pump with
‘O’ Reversing Valve.
8 Wire, 2 Stage Cooling, 4 Stage Heat
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
W2 3rd Stage Heat
W3 4th Stage Heat
Y1 1st Stage Compressor
(Cool or Heat)
Y2 2nd Stage Compressor
(Cool or Heat)
G Fan
Residential & Commercial Heat Pump with
‘O’ Reversing Valve
6 Wire, 1 Stage Cooling, 2 Stage Heat
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
Y1 1st Stage Compressor
(Cool or Heat)
W2 Aux Heat
G Fan
Residential & Commercial Heat Pump with
‘O’ Reversing Valve.
7 Wire, 2 Stage Cooling, 3 Stage Heat
R 24VAC Power
C 24VAC Common
W1/O/B Reversing Valve
W2 3rd Stage Heat
Y1 1st Stage Compressor
(Cool or Heat)
Y2 2nd Stage Compressor
(Cool or Heat)
G Fan
(Number of Compressor Stages set to 2)
(Number of Compressor Stages set to 2)
GAS/EL
HP
O
GAS
B
ELEC
GAS/EL
HP
O
GAS
B
ELEC
GAS/EL
HP
O
GAS
B
ELEC
GAS/EL
HP
O
GAS
B
ELEC
12
3
ON
12
3
ON
12
3
ON
12
3
ON
Sample Wiring Diagrams with Dip Switch Positions
Heat Pump Systems
Installation Instructions –
Sample Wiring Diagrams
Содержание OEM Series
Страница 58: ...Manual Installer Guide 50 The user may limit the maximum Cooling Setpoint Main Menu Buttons Settings...
Страница 59: ...51 Manual Installer Guide The user may limit the minimum Heating Setpoint Main Menu Buttons Settings...
Страница 60: ...Manual Installer Guide 52 2 The user may adjust the ADR Cooling static Setpoint Main Menu Buttons Settings...
Страница 61: ...53 Manual Installer Guide 2 The user may adjust the ADR Heating static Setpoint Main Menu Buttons Settings...
Страница 94: ......
Страница 95: ......