PLX51-DL-232
RSLogix 5000 Configuration
Data Logger
User Manual
ProSoft Technology, Inc.
Page 30 of 59
4 RSLogix 5000 Configuration
4.1 Add Module to I/O Configuration
The PLX51-DL-232 can operate in both a Logix “owned” and standalone mode. When
the PLX51-DL-232 operates in a Logix “owned” mode, the PLX51-DL-232 needs to be
added to the RSLogix 5000 / Studio5000 IO tree, as a generic Ethernet module.
1
Right-click on the Ethernet Bridge in RSLogix 5000 and select
New Module
. Then
select
ETHERNET-MODULE
and click
Ok
.
Figure 4.1 - Add a Generic Ethernet Module in RSLogix 5000
2
Enter the IP address of the PLX51-DL-232. The
Assembly Instance
and
Size
must
also be added for the input, output, and configuration in the
Connection Parameters
section. Below are the required connection parameters.
Table 4.1 - RSLogix class 1 connection parameters for the Data Logger
Connection Parameter
Assembly Instance
Size
Input
103
29 (32-bit)
Output
104
1 (32-bit)
Configuration
102
0 (8-bit)