The following illustration shows the layout of the databases:
Data contained in this database is paged through the BTR and BTW images by
coordination of the PLC ladder logic and the MVI71-DNPSNET module's
program. Up to 64 words of data can be transferred from the module to the
processor at a time. Up to 64 words of data can be transferred from the
processor to the module.
Each block transferred from the module to the processor or from the processor to
the module contains a block identification code that describes the content of the
block. The following table defines the blocks used by this module:
Block Number
Function/Description
0 or -1
Dummy Blocks: Used by module when no data is to be transferred
1 to 149
DNP Data blocks
1000 to 1148
Output initialization blocks
9958
PLC Binary Input Event data
9959
PLC Analog Input Event Data
9970
Set PLC time using module's DNP time
9971
Set module's time using PLC time
9998
Warm Boot Request from PLC (Block contains no data)
9999
Cold Boot Request from PLC (Block contains no data)