![ProSoft Technology InRax MVI71-DNPSNET Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/prosoft-technology/inrax-mvi71-dnpsnet/inrax-mvi71-dnpsnet_user-manual_1618934043.webp)
Diagnostics and Troubleshooting
MVI71-DNPSNET
♦
PLC Platform
Distributed Network Protocol Interface Module
ProSoft Technology, Inc.
Page 43 of 100
September 22, 2008
4.2
LED Status Indicators
The LEDs indicate the module's operating status as follows:
ProSoft
Module
Color Status Indication
On
Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.
CFG Green
Off
No data is being transferred on the Configuration/Debug port.
On
Port not used
P1 Green
Off
Port not used
On
Port not used
P2 Green
Off
Port not used
Off
The MVI71-DNPSNET is working normally.
APP Status Amber
On
The MVI71-DNPSNET module program has recognized a
communication error on one of its DNP ports.
On
The LED is on when the module is performing a write
operation on the backplane.
BP Amber
Off
The LED is off when the module is performing a read
operation on the backplane. Under normal operation, the LED
should blink rapidly on and off.
Off
The card is not receiving any power and is not securely
plugged into the rack.
Green
The module is operating normally.
OK Red/
Green
Red
The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-insert
the card to restart the module's program.
Off
The battery voltage is OK and functioning.
BAT Red
On
The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.
In addition to these LEDs, the module contains two LEDs under the module's
door. The LED on the left (green) displays the link status. If the module is
connected properly to a hub, this LED should be illuminated. The LED on the
right (amber) is the data indication LED. Whenever the module is sending or
receiving data on the Ethernet interface, this LED is illuminated.
4.2.1 Ethernet LED Indicators
LED State
Description
Off
No activity on the port.
Data
Green Flash
The port is either actively transmitting or receiving data.
Off
No connection to hub or network is detected.
Link
Green Solid
Connected to hub or network correctly. This is the normal
operating state.
Содержание InRax MVI71-DNPSNET