MVI56-HART ♦ ControlLogix Platform
Reference
HART Multi-drop Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 93 of 171
October 13, 2011
DB Byte
Offset
Type
Description
Byte
Cnt
Data
Source
Use of Data
60 to 63
float
Primary variable value
4
CMD 3
Status
64 to 67
float
Secondary variable value
4
CMD 3
Status
68 to 71
float
Tertiary variable value
4
CMD 3
Status
72 to 75
float
Quaternary variable value
4
CMD 3
Status
76 to 79
float
Upper transducer limit
4
CMD 14 Cfg
80 to 83
float
Lower transducer limit
4
CMD 14 Cfg
84 to 87
float
Minimum span
4
CMD 14 Cfg
88 to 91
float
PV upper range value
4
CMD 15 Cfg
92 to 95
float
PV lower range value
4
CMD 15 Cfg
96 to 99
float
PV damping value (in seconds)
4
CMD 15 Cfg
TOTAL FLOAT BYTE COUNT
40
TOTAL FLOAT WORD COUNT
20
DB Regs/Device
50
Max DB Regs/channel for 15 Devices
750
Max DB Regs for HART Card
3000
The following table defines the auto-polling command status bits:
Bit #
Description
0
Long Address Set (command 0 successful)
1
Command 13 successful (configuration)
2
Command 14 successful (configuration)
3
Command 15 successful (configuration)
4
Command 3 successful (data polling)
5
Reserved
6
Reserved
7
Reserved
The following topics describe the modes of module operation.
Auto-Poll Disabled Mode
If the auto-polling feature is disabled (Auto-Poll Code = N), the module functions as
shown in the following diagram:
Only the user commands are executed and all data is placed in and sourced from the
module's internal database. The user is responsible for constructing all commands to
control and monitor the instruments attached to the channel.