Contents
ILX69-PBS ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS Slave Communication Module
Page 46 of 102
ProSoft Technology, Inc.
April 27, 2016
5.2.3 Configuration by Controller Application
The second option to configure the ILX69-
PBS is through the controller application. If you’re
unable to install the AOP due to company policy or other reasons, you will need to manually
configure the module through the controller application.
The "Force User Config" parameter in this array must be set to 1. With this method, the
ILX69-PBS will not start any network communication unless the master and ILX69-PBS
configuration match. The following table outlines the mapping of the configuration data
image.
Word
Offset
Configuration
word
Data
type
Low/High
Byte
Description
Valid values
0
Local:1:C.Data[0]
INT
LOW Byte
Reconfiguration Event 0
Reserved, set to 0
HIGH Byte
Reconfiguration Event 1
1
Local:1:C.Data[1]
INT
LOW Byte
Reconfiguration Event 2
Reserved, set to 0
HIGH Byte
Reconfiguration Event 3
2
Local:1:C.Data[2]
INT
LOW Byte
Bus Address
0 to 125
0 = ForceMasterConfig
1 = ForceUserConfig
HIGH Byte
Force User Configuration
3
Local:1:C.Data[3]
INT
Reserved
4
Local:1:C.Data[4]
INT
Watchdog Time
0 to FFFFh
5
Local:1:C.Data[5]
INT
Number of valid config bytes
(starting with Local:1:C.Data[8])
2 to 48
6
Local:1:C.Data[6]
INT
Reserved
7
Local:1:C.Data[7]
INT
Reserved
8
Local:1:C.Data[8]
INT
LOW Byte
Module 1 Type
HIGH Byte
Module 1 Length
9
Local:1:C.Data[9]
INT
LOW Byte
Module 2 Type
HIGH Byte
Module 2 Length
...
...
...
...
31
Local:1:C.Data[31]
INT
LOW Byte
Module 24 Type
HIGH Byte
Module 24 Length
32
Local:1:C.Data[32]
BOOL -
IP Config flags 1, Static or
Dynamic
0 or 1
33
Local:1:C.Data[33]
BOOL -
IP Config flags 2, Static or
Dynamic
0 or 1
34
Local:1:C.Data[34]
INT
-
IP Configuration
0 = BOOTP
1 = DHCP
2 = FIXED IP
35
Local:1:C.Data[35]
SINT
LOW Byte
IP Address
00.00.00.00 through
FF.FF.FF.FF
…
…
HIGH Byte