![ProSoft Technology ILX34-MBS Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/prosoft-technology/ilx34-mbs/ilx34-mbs_user-manual_1618917025.webp)
ILX34-MBS
User Manual
Configuration
ProSoft Technology, Inc.
Page 25 of 29
3.7
Data Handling
The following PLC data tags are used for the Master and Slave. For the Master, the tags
represent the
module’s internal addresses. For the Slave, the tags represent the
addresses accessed by a remote Master.
Parameter
Description
InputBit
Incoming discreet data for address ranges 0x and 1x from
other devices. Functions 5 and 15 when device is configured
as a Slave. Functions 1 and 2 when configured as a Master.
InputRegister
Incoming register data for address ranges 3x and 4x from
other devices. Functions 6 and 16 when device is configured
as a Slave. Functions 3 and 4 when configured as a Master.
OutputBit
Outgoing discreet data for address ranges 0x and 1x from
other devices. Functions 1 and 2 when device is configured as
a Slave. Functions 5 and 15 when configured as a Master.
OutputRegister
Outgoing register data for address ranges 3x and 4x from
other devices. Functions 3 and 4 when device is configured as
a Slave. Functions 6 and 16 when configured as a Master.