ILX34-MBS
User Manual
Configuration
ProSoft Technology, Inc.
Page 21 of 29
3.4.3 Configuring the ILX34-MBS Modbus Serial Port
1
Double-click
Controller Tags
from the
Controller Organizer
.
2
Expand the
MBS_Config
controller tag.
3
Set the following parameters to configure the Serial Port.
Parameter
Description
Baud Rate
0 = 19200
2 = 2400
3 = 4800
4 = 9600
5 = 38400
Serial Comm
0 = 7N2
1 = 7E1
2 = 7O1
3 = 8N1
4 = 8N2
5 = 8E1
6 = 8O1
Protocol
0 = ASCII
1 = RTU