PRS-UM-DP8-EN-Rev.4.1-16.08.2021 

3.

 

Turn off the gas supply at the tap and/or on the gas bottle (in the case of LPG). 

4.

 

Do not switch electrical appliances, lamps or the gas detection control unit on or off. 

5.

 

Open all windows and doors to air the room. 

6.

 

Do not “reset” the control unit if it is in the same room. 

If the gas concentration reading on the control unit does not fall below the level of alarm, 
and the reason for the gas leak is not immediately apparent and/or cannot be repaired, quit 
the premises and call the gas supplier and/or emergency services immediately to check the 
installations and to make the premises safe and to possibly carry out the necessary repairs. 
If the alarm stops and the reason for the alarm is identified and resolved (e.g. a kitchen 
burner lit off but in the open position) the gas supply may be re-opened after checking that 
all the gas appliances are off. 

Controlling the Alarm Fault Functions 

PROBLEMS  

POSSIBLE CAUSES  

WHAT TO CHECK 

The display is not on 

Main power source is 

OFF 

Check the Main power connection 

 

Bad power supply. 

Check the power supply. The green 

LED should be on 

 

Blown fuse(s). 

Check fuses on main power 

connection and replace if necessary. 

BATTERY LED is ON 

No line power, System is 

using Backup battery 

Check line power and related fuses 

 

Power supply range is 

below 27 V 

Adjust power supply output level via 

Phillips screwdriver 

FAULT LED is ON and FLT 

sign shown on LCD screen 

The Detector 

connection is broken 

Check the detector cables 

 

The detector output 

signal is too low 

If detector is working fine the output 

current might be getting low at 

control panel input. Adjust the zero 

level of the detector. 

There is no detector 

connected to channel 

Close (deactivate) related channel via 

using menu steps 

Detector is faulty 

Check detector connected to channel 

ALARM1 and/or ALARM2 

and/or AUX LED is ON 

There is a gas leak. 

Close the manual valve on the gas 

input pipe. Locate and repair the leak.  

ALARM1 and/or ALARM2 

and/or AUX LED is ON and 

there is no gas leak 

The control panel has 

false alarms 

Reset control panel 

 

Alarms might stuck due 

to previous gas leak 

Press EXIT button for 5 seconds to 

reset the panel 

Table 

9

: Problems and possible causes

 

Содержание S-DP8

Страница 1: ...P8 EN Rev 4 1 16 08 2021 PROSENSE S DP8 Gas Control Panel User Manual Prosense Teknoloji San Ltd ti Cumhuriyet Mah Mermer sok No 16 Kartal stanbul Tel 90 216 306 77 88 Faks 90 216 473 81 29 www prosen...

Страница 2: ...rwise it could fail to perform as designed and persons who rely on this product for their safety could suffer severe personal injury or death The warranties made by Prosense with respect to this produ...

Страница 3: ...kup Battery Connection 13 Main Power Connection 13 Detectors Connections 14 Relay Outputs 14 AUX Relay Output 15 First Run 15 Automatic Test 15 Programming 16 Setup Channel Parameters 16 Closing Unuse...

Страница 4: ...rm which are adjustable according to the measuring range and one fault alarm for the detection loop Individual relays per function ensure remote controlled output There are 4 relays on the panel Two o...

Страница 5: ...Alarm LEDs for each detector channel Backup battery 12V 7A h Optional X 2 Operating Temp 10 60 C0 Humidity 15 95 non condensing Housing ABS IP66 546 X 276 X 186 mm Weight 5 75 kg Main power fuse 2A Ba...

Страница 6: ...avoid any accidentally damaging S DP8 control panel should not be placed nearby high voltage cables or power cable coaxial cables or transmitters welding stations or frequency regulators The S DP8 pa...

Страница 7: ...ront cover M4 screws are suitable to fix the panel body to the wall Once wall mounting completed reattached the front cover and tighten 6 plastic screws To prepare cable entries remove plastic cover f...

Страница 8: ...anel body Plastic screws Plastic screws Backup battery connectors and fuse Power supply N L G V V Wall mounting hole Wall mounting hole Main power entry and fuse Space for backup batteries Power suppl...

Страница 9: ...ion For Configuration Function For Display Operation MENU Enter to panel configuration OK Select key UP Go to upper menu option during configuration Page change on main screen DOWN Go to lower menu op...

Страница 10: ...details If there is no detector connected to channel LCD screen will show it as FLT and fault LED will be activated That channel should be closed deactivated via using menu steps The LCD screen brilli...

Страница 11: ...screen on related channel with Range symbol and measurement level fixed to 99LEL The overrange condition is highest measurement level that panel can understand and overrange level is higher than alar...

Страница 12: ...n it is run off There are five sockets on the main board to install optional relay modules Each relay module has 8 relay on it and each relay controlled by one detector It is possible to take independ...

Страница 13: ...anel is in alarm status for a long time Backup Battery Connection To continue operation in case of main power failure two backup batteries 12V 7Ah must be serially connected to the system Take extra c...

Страница 14: ...tors In case less than 8 detectors used the system will raise fault status for unused channels and overall panel status remain in fault status In this case user should close deactivate unused channels...

Страница 15: ...LARM3 is selected AUX relay will be active by the digital input on the panel In case of any alarm signal received from external device it will be shown in 9th line on LCD as digital alarm First Run Pa...

Страница 16: ...Monitor software To activate configuration menu press and hold the MENU button for a second You can navigate between the menu items via using the UP and DOWN keys Press MENU key again to enter submenu...

Страница 17: ...and PPM Once selected press MENU button Then screen will display Range options You can select below values for range For LEL 0 50 or 0 100 For VOL 0 5 or 0 25 or 0 30 For PPM 0 10 or 0 20 or 0 30 or 0...

Страница 18: ...and DOWN buttons 10 Once all completed press exit button to return the previous screen Alarm1 level cannot be higher than Alarm2 level Hence it would be easier to adjust Alarm2 level first before adju...

Страница 19: ...Assignment The alarm relays work only in latched mode Therefore the relay will not be released and stay in active mode till manual intervention Even after environment is cleaned following an alarm con...

Страница 20: ...be set prior to start communication Each panel located on same serial connection bus should have different ID Panel ID can be set via using the LCD screen and menu buttons on panel itself Please pres...

Страница 21: ...em there are two alarms one fault one power and one battery LED used to monitor overall panel status ALARM1 and ALARM2 LEDs will be activated and kept active when any of the detectors raised an alarm...

Страница 22: ...r source is OFF Check the Main power connection Bad power supply Check the power supply The green LED should be on Blown fuse s Check fuses on main power connection and replace if necessary BATTERY LE...

Страница 23: ...23 PRS UM DP8 EN Rev 4 1 16 08 2021 Declaration...

Страница 24: ...any fault is not found with the equipment Prosense Technology shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or opera...

Отзывы: