Prosense S-DP8 Скачать руководство пользователя страница 14

 

 

14 

PRS-UM-DP8-EN-Rev.4.1-16.08.2021 

Detectors Connections 

Panel can be connected and monitor 8 detectors with 4-20 mA output signal. V+, V-(GND) 
and S ports must be connected via using three-wire cable. Detector connections supply 24 
VDC power to detector and read the output signal of detector from S port. Thus connections 
should be made correctly to do not cause any damage on the detectors. Detectors should be 
connected with three-wire 0.5mm

2

  cross section cable. Cable diameter will be increased 

while distance increase between the panel and detectors.  Recommended cable types per 
distance are given in table 6: 

Cable size 

Cable type 

Cable resistance 

Maximum Cable length (L) 

(cross sectional area) 

nearest equivalent 

Ω/km

 

Meters 

0.5 mm2 

20 AWG 

36.8 Ω/km

 

400 

1.0 mm2 

17 AWG 

19.5 Ω/km

 

750 

1.5 mm2 

16 AWG 

12.7 Ω/km

 

1000 

2.0 mm2 

14 AWG 

10.1 Ω/km

 

1250 

2.5 mm2 

13 AWG 

8.0 Ω/km

 

1500 

Table 

7: 

Typical cable details and maximum distance for cabling

 

Detector connections should be made with 3 core cable and pin definitions are as follows: 

4-20 mA signal 

GND   (V-) 

Supply (V+) 

Table 

8: Connection pin definitions 

The panel is programmed as all channels in operation and connected to detectors. In case 
less than 8 detectors used the system will raise fault status for unused channels and overall 
panel status remain in fault status. In this case user should close (deactivate) unused 
channels via using configuration menu steps. 

Relay Outputs 

S-DP8 panel has four relay outputs which are ALARM1, ALARM2, FAULT and AUX. Relay 
connection ports are located right under the relays. Alarm relays are operating in latched 
mode. Hence the panel will wait user intervention to clear alarm status even conditions 
returned to normal. User should reset status via pressing Exit button to acknowledge any 
alarm. The active relays can also be monitored via related LEDs on the panel. Relay details 
and activation rules are given below: 

ALARM1: 

This relay will be activated when any of the detectors in the system will exceed the 

programmed Alarm-1 level threshold. If there is oxygen detector used in the system, 
ALARM1 is also used as the low oxygen level alarm. 

ALARM2: 

This relay will be activated when any of the detectors in the system will exceed the 

programmed Alarm-2 threshold level. If there is oxygen detector used in the system, 
ALARM2 is also used as the high oxygen level alarm. 

FAULT: 

This relay is normally energised, and it will be de-energised when any of the internal 

fault detection measures detects a fault. The Fault LED will be activated also when line 

Содержание S-DP8

Страница 1: ...P8 EN Rev 4 1 16 08 2021 PROSENSE S DP8 Gas Control Panel User Manual Prosense Teknoloji San Ltd ti Cumhuriyet Mah Mermer sok No 16 Kartal stanbul Tel 90 216 306 77 88 Faks 90 216 473 81 29 www prosen...

Страница 2: ...rwise it could fail to perform as designed and persons who rely on this product for their safety could suffer severe personal injury or death The warranties made by Prosense with respect to this produ...

Страница 3: ...kup Battery Connection 13 Main Power Connection 13 Detectors Connections 14 Relay Outputs 14 AUX Relay Output 15 First Run 15 Automatic Test 15 Programming 16 Setup Channel Parameters 16 Closing Unuse...

Страница 4: ...rm which are adjustable according to the measuring range and one fault alarm for the detection loop Individual relays per function ensure remote controlled output There are 4 relays on the panel Two o...

Страница 5: ...Alarm LEDs for each detector channel Backup battery 12V 7A h Optional X 2 Operating Temp 10 60 C0 Humidity 15 95 non condensing Housing ABS IP66 546 X 276 X 186 mm Weight 5 75 kg Main power fuse 2A Ba...

Страница 6: ...avoid any accidentally damaging S DP8 control panel should not be placed nearby high voltage cables or power cable coaxial cables or transmitters welding stations or frequency regulators The S DP8 pa...

Страница 7: ...ront cover M4 screws are suitable to fix the panel body to the wall Once wall mounting completed reattached the front cover and tighten 6 plastic screws To prepare cable entries remove plastic cover f...

Страница 8: ...anel body Plastic screws Plastic screws Backup battery connectors and fuse Power supply N L G V V Wall mounting hole Wall mounting hole Main power entry and fuse Space for backup batteries Power suppl...

Страница 9: ...ion For Configuration Function For Display Operation MENU Enter to panel configuration OK Select key UP Go to upper menu option during configuration Page change on main screen DOWN Go to lower menu op...

Страница 10: ...details If there is no detector connected to channel LCD screen will show it as FLT and fault LED will be activated That channel should be closed deactivated via using menu steps The LCD screen brilli...

Страница 11: ...screen on related channel with Range symbol and measurement level fixed to 99LEL The overrange condition is highest measurement level that panel can understand and overrange level is higher than alar...

Страница 12: ...n it is run off There are five sockets on the main board to install optional relay modules Each relay module has 8 relay on it and each relay controlled by one detector It is possible to take independ...

Страница 13: ...anel is in alarm status for a long time Backup Battery Connection To continue operation in case of main power failure two backup batteries 12V 7Ah must be serially connected to the system Take extra c...

Страница 14: ...tors In case less than 8 detectors used the system will raise fault status for unused channels and overall panel status remain in fault status In this case user should close deactivate unused channels...

Страница 15: ...LARM3 is selected AUX relay will be active by the digital input on the panel In case of any alarm signal received from external device it will be shown in 9th line on LCD as digital alarm First Run Pa...

Страница 16: ...Monitor software To activate configuration menu press and hold the MENU button for a second You can navigate between the menu items via using the UP and DOWN keys Press MENU key again to enter submenu...

Страница 17: ...and PPM Once selected press MENU button Then screen will display Range options You can select below values for range For LEL 0 50 or 0 100 For VOL 0 5 or 0 25 or 0 30 For PPM 0 10 or 0 20 or 0 30 or 0...

Страница 18: ...and DOWN buttons 10 Once all completed press exit button to return the previous screen Alarm1 level cannot be higher than Alarm2 level Hence it would be easier to adjust Alarm2 level first before adju...

Страница 19: ...Assignment The alarm relays work only in latched mode Therefore the relay will not be released and stay in active mode till manual intervention Even after environment is cleaned following an alarm con...

Страница 20: ...be set prior to start communication Each panel located on same serial connection bus should have different ID Panel ID can be set via using the LCD screen and menu buttons on panel itself Please pres...

Страница 21: ...em there are two alarms one fault one power and one battery LED used to monitor overall panel status ALARM1 and ALARM2 LEDs will be activated and kept active when any of the detectors raised an alarm...

Страница 22: ...r source is OFF Check the Main power connection Bad power supply Check the power supply The green LED should be on Blown fuse s Check fuses on main power connection and replace if necessary BATTERY LE...

Страница 23: ...23 PRS UM DP8 EN Rev 4 1 16 08 2021 Declaration...

Страница 24: ...any fault is not found with the equipment Prosense Technology shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or opera...

Отзывы: