In case any panel self-test result reports a fault 

 

In case panel main power lost and while panel is working with battery power 

 

In case panel main power supply fails 

This status has been detected by panel when an input signal is below 3.5 mA and reported 
on LCD screen on related channel with “FLT” symbol. Panel will activate FAULT relay and LED 
in case of any fault. Panel also activate fault LED for related channel if the fault status 
detected on a detector channel. 
Fault relay is normally energised, and it will be de-energised when any of the internal fault 
detection measures detects a fault. The Fault LED will be activated also when line power is 
lost and system runs with battery power. It is also possible to get an alarm when control 
panel totally loses the power. 

Overrange Status:

 

The panel reports  overrange status in case any of the channels reported measurement 
higher than measurement range. This  status  has been detected by panel  when an input 
signal is over range (> 20 mA) and reported on LCD screen on related channel with “

Range<

” 

symbol  and measurement level fixed to 99LEL. The overrange condition is highest 
measurement level that panel can understand  and  overrange level is higher than alarm 
levels. The alarm LEDs and relays will be activated before panel reports overrange condition. 

 

Diagram 10: Overrange status indication 

Alarm Status: 

The Panel will report Alarm status when gas level exceeds defined alarm levels on any of the 
detector channel. Panel has two adjustable measurement alarm levels. If any connected 
detector measurement reaches the given alarm threshold level, panel will activate related 
alarm relay and LED. Alarm-1 relay and LED will be activated in case any of the connected 
detector measurement reaches defined Alarm-1 threshold level. Panel will show "AL1" 
symbols for the related channel on LCD screen and also activate alarm  LED on related 
channel. Alarm-2 relay and LED will be activated in case any of the connected detector 
measurement reaches defined Alarm-2 threshold level. Panel will show "AL2" symbol for the 
related channel on LCD screen and also activate alarm LED on related channel. Alarm-1 and 
Alarm-2 relays and LEDs will be both active in case any of the connected detector reports 
Alarm-2 status. 

Содержание S-DP8

Страница 1: ...P8 EN Rev 4 1 16 08 2021 PROSENSE S DP8 Gas Control Panel User Manual Prosense Teknoloji San Ltd ti Cumhuriyet Mah Mermer sok No 16 Kartal stanbul Tel 90 216 306 77 88 Faks 90 216 473 81 29 www prosen...

Страница 2: ...rwise it could fail to perform as designed and persons who rely on this product for their safety could suffer severe personal injury or death The warranties made by Prosense with respect to this produ...

Страница 3: ...kup Battery Connection 13 Main Power Connection 13 Detectors Connections 14 Relay Outputs 14 AUX Relay Output 15 First Run 15 Automatic Test 15 Programming 16 Setup Channel Parameters 16 Closing Unuse...

Страница 4: ...rm which are adjustable according to the measuring range and one fault alarm for the detection loop Individual relays per function ensure remote controlled output There are 4 relays on the panel Two o...

Страница 5: ...Alarm LEDs for each detector channel Backup battery 12V 7A h Optional X 2 Operating Temp 10 60 C0 Humidity 15 95 non condensing Housing ABS IP66 546 X 276 X 186 mm Weight 5 75 kg Main power fuse 2A Ba...

Страница 6: ...avoid any accidentally damaging S DP8 control panel should not be placed nearby high voltage cables or power cable coaxial cables or transmitters welding stations or frequency regulators The S DP8 pa...

Страница 7: ...ront cover M4 screws are suitable to fix the panel body to the wall Once wall mounting completed reattached the front cover and tighten 6 plastic screws To prepare cable entries remove plastic cover f...

Страница 8: ...anel body Plastic screws Plastic screws Backup battery connectors and fuse Power supply N L G V V Wall mounting hole Wall mounting hole Main power entry and fuse Space for backup batteries Power suppl...

Страница 9: ...ion For Configuration Function For Display Operation MENU Enter to panel configuration OK Select key UP Go to upper menu option during configuration Page change on main screen DOWN Go to lower menu op...

Страница 10: ...details If there is no detector connected to channel LCD screen will show it as FLT and fault LED will be activated That channel should be closed deactivated via using menu steps The LCD screen brilli...

Страница 11: ...screen on related channel with Range symbol and measurement level fixed to 99LEL The overrange condition is highest measurement level that panel can understand and overrange level is higher than alar...

Страница 12: ...n it is run off There are five sockets on the main board to install optional relay modules Each relay module has 8 relay on it and each relay controlled by one detector It is possible to take independ...

Страница 13: ...anel is in alarm status for a long time Backup Battery Connection To continue operation in case of main power failure two backup batteries 12V 7Ah must be serially connected to the system Take extra c...

Страница 14: ...tors In case less than 8 detectors used the system will raise fault status for unused channels and overall panel status remain in fault status In this case user should close deactivate unused channels...

Страница 15: ...LARM3 is selected AUX relay will be active by the digital input on the panel In case of any alarm signal received from external device it will be shown in 9th line on LCD as digital alarm First Run Pa...

Страница 16: ...Monitor software To activate configuration menu press and hold the MENU button for a second You can navigate between the menu items via using the UP and DOWN keys Press MENU key again to enter submenu...

Страница 17: ...and PPM Once selected press MENU button Then screen will display Range options You can select below values for range For LEL 0 50 or 0 100 For VOL 0 5 or 0 25 or 0 30 For PPM 0 10 or 0 20 or 0 30 or 0...

Страница 18: ...and DOWN buttons 10 Once all completed press exit button to return the previous screen Alarm1 level cannot be higher than Alarm2 level Hence it would be easier to adjust Alarm2 level first before adju...

Страница 19: ...Assignment The alarm relays work only in latched mode Therefore the relay will not be released and stay in active mode till manual intervention Even after environment is cleaned following an alarm con...

Страница 20: ...be set prior to start communication Each panel located on same serial connection bus should have different ID Panel ID can be set via using the LCD screen and menu buttons on panel itself Please pres...

Страница 21: ...em there are two alarms one fault one power and one battery LED used to monitor overall panel status ALARM1 and ALARM2 LEDs will be activated and kept active when any of the detectors raised an alarm...

Страница 22: ...r source is OFF Check the Main power connection Bad power supply Check the power supply The green LED should be on Blown fuse s Check fuses on main power connection and replace if necessary BATTERY LE...

Страница 23: ...23 PRS UM DP8 EN Rev 4 1 16 08 2021 Declaration...

Страница 24: ...any fault is not found with the equipment Prosense Technology shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or opera...

Отзывы: