18
PRS-UM-DP32-EN-Rev.02-05.2019
Programming
The panel is already programmed and ready for using when shipped. User should adjust the
alarm settings via changing alarm levels for each channel depending on the detectors
installed. Each channel parameters should be adjusted regarding related detector
measurement unit and range. These adjustments can be done via using the keys nearby LCD.
Each detector can also be named in the menu. The menu steps are given in Diagram 11.
Diagram 16: Menu
structure
S-DP32 control panel keeps data and time information to record alarm events in the internal
log space. The alarm logs menu is not available when panel uses RS485 module to
communicate to Prosense Panel Monitor software.
To activate configuration menu, press and hold the MENU button for a second. You can
navigate between the menu items via using the UP and DOWN keys. Press MENU key again
to enter submenu. You can EXIT from submenu or menu by pressing the EXIT button.
1.
Channel setting
2.
Time / Language settings
3.
Relay assignment
4.
Alarm logs
Single Channel Mode:
To see each detector status in detail, press UP button on the main menu. Screen will switch
in to single channel mode. Then it will display detector status, instant reading value, alarm
status and detector name:
If there is any fault or alarm it will be displayed right bottom corner of screen:
1- Channel setting
2- Time/Language settings
3- Relay assignment
4-
Alarm logs
1. Detectr.
2. Detectr.
3. Detectr.
4. Detectr.
MENU
1-Detector Setting
Aux > Alarm2
Alarm > automatic
hour. min. sec day/
month/ year
4-Alarm logs
2-Time Setting
3-Relay Assign
1>D4 F3 23/06 15:55
2>D3 A1 23/06 12:12
Main menu screen