17
PRS-UM-DP32-EN-Rev.02-05.2019
battery power. The Fault relay is energised and it is possible to get an alarm when control
panel totally lost the power
If needed user can obtain independent alarm and fault outputs from each detector via using
optional relay module. Relay modules should be installed reserved zone sockets explained
earlier. The relays are configured as NO (normally open) by default at factory. The relay
configurations can be adjusted via putting jumpers under each relay. Relay will not provide
output while jumpers are omitted or not installed. Relay connections pins are:
NC
: Normally closed contact pin (Select by jumper under relay)
NO
: Normally open pin (Select by jumper under relay)
COM : Common pin
Not
e
:
Relays should not be connected to high current or 220V AC loads. The relay outputs
should be used as control signal and external relays should be used to drive such devices as
relay on main board cannot handle high load.
AUX Relay Output
Aux relay can be programmed from the main menu on the panel to match to ALARM1,
ALARM2 or ALARM3. When ALARM1 is selected, AUX relay will operate simultaneously with
ALARM1 relay of the system. When ALARM2 is selected, AUX relay will be active when
ALARM2 relay activated. When ALARM3 is selected, AUX relay will be active by the digital
input on the panel. In case of any alarm signal received from external device it will be shown
in 9th line on LCD as digital alarm.
First Run
Panel manufacturer (Prosense) and model (S-DP32) will be seen on LCD screen following the
power-up. All LEDs on the panel and sounder device will be activated for 3 seconds. The user
can recognize any malfunctioning LED on panel at this period. The Fault relay and LED will be
activated during the warm-up period. The panel will start searching channels one by one and
activate the channel power and fault LEDs. This operation may take two minutes. During this
period, system will operate in standby mode until the detectors are warmed up.
Instantaneous alarms will be turned off during the warm-up period.
Panel will list recognized detectors on LCD screen with their current status information.
Automatic Test
S-DP32 gas control panel simultaneously monitor all detectors connected to it. Panel should
have power LED and connected detector Channel ON LEDs during normal operation. S-DP32
panel also runs internal component tests at the warm-up time and every 8 hours. The FAULT
relay and LED will be activated in case any problem. Alarm and fault status can be monitored
on the screen and via checking related detector LEDs.