background image

 

ISQB1 Installation Guide - 2/13/2015 | SSS 

DESCRIPTION / IDENTIFICATION 

 

The  ISQB1  series  control  valve  is  an  electronic 
pressure  regulator  designed  to  precisely  and 
proportionally  control  the  pressure  of  gaseous  media 
based on an electronic control signal. 
 
The  ISQB1  operates  using  two  normally  closed 
solenoid  valves,  a  pressure  sensor,  and  a  control 
circuit.    One  valve  is  actuated  to  allow  supply  media 
into the system.  The second valve is actuated to allow 
working  media  to  vent  through  a  threaded  port  to 
atmosphere.   The  pressure  sensor  provides feedback 
to the control circuit.  The control circuit compares the 
pressure  sensor  feedback  to  the  user  supplied 
electronic  command  signal  and  actuates  the 
appropriate valve until the two signals match. 
 
The ISQB1 series can be teamed with a variety of air 
piloted  pressure  volume  boosters  for  even  greater 
flow.   

† 

Pressure ranges are customer specified. Output pressures other 

than 100% are available. 

ELECTRICAL 

SUPPLY VOLTAGE  13.9 to 29 VDC (MAX) 

SUPPLY CURRENT  < 80 mA 

COMMAND SIGNAL  4-20 mA Differential 

COMMAND SIGNAL IMPEDANCE  Current=100 Ω 

MECHANICAL 

PRESSURE RANGES  Full Vacuum - 150 psig 

 

(29.9 in. HG (Vac) - 10.3 Bar) 

OUTPUT PRESSURE†  0-100% of range 

FLOW RATE  0.80 SCFM @ 80 PSIG 

 

(23 L/min @ 5.52 Bar) 

Min CLOSED END VOLUME  1 in

3

 

PORT SIZE  1/8” NPT 

FILTRATION RECOMMENDED  20 Micron 

(included)

 

LINEARITY/HYSTERESIS  <±0.15% F.S. BFSL 

REPEATABILITY  <±0.02% F.S. 

ACCURACY  <±0.2% F.S. 

PHYSICAL 

OPERATING TEMERPATURE  32-104°F 

(0-40°C) (T4)

 

WEIGHT  2.5 lbs. 

(1.1 Kg)

 

PROTECTION RATING  NEMA 4 

HOUSING  Blue Anodized Aluminum 

SPECIFICATIONS 

HAZARDOUS AREA CLASSIFICATION

 

 

The ISQB is rated Intrinsically Safe and is 
Factory  Mutual  approved  for  Class  I,  II  & 
III, Division 1, Groups C, D, E, F & G 

 
Entity Parameters: 

 

V Max  = 29 VDC 

 

I Max    = 150 MA 

 

Ci 

= 0.26uF 

 

Li 

= 0 

 

Field Wiring Drawing: 

ISQB-96026-2

 

 
NOTES:   

End  user  must  determine  fitness  and 

suitability  of  the  ISQB1  control  valve  for  their  application. 
The ISQB requires the use of Intrinsically Safe Barriers. 

PROPORTION-AIR, INC. 

8250 N. 600 West 
McCordsville, IN 46055 
 
877.331.1738 

[email protected] 

WETTED MATERIALS 

PARAMTERS 

Port 1 (Pressure Port) 

Port 2 (Reference Port) 

COVERS 

High Temperature Polyamide 

High Temperature Polyamide 

SUBSTRATE 

Alumina Ceramic 

Alumina Ceramic 

ADHESIVES 

Epoxy, RTV 

Epoxy, RTV 

ELECTRONIC COMPONENTS 

Ceramic, Silicon 

Silicon, Glass, Gold, Solder 

INSTALLATION & MAINTENANCE INSTRUCTIONS

 

Содержание ISQB1

Страница 1: ...urrent 100 Ω MECHANICAL PRESSURE RANGES Full Vacuum 150 psig 29 9 in HG Vac 10 3 Bar OUTPUT PRESSURE 0 100 of range FLOW RATE 0 80 SCFM 80 PSIG 23 L min 5 52 Bar Min CLOSED END VOLUME 1 in3 PORT SIZE 1 8 NPT FILTRATION RECOMMENDED 20 Micron included LINEARITY HYSTERESIS 0 15 F S BFSL REPEATABILITY 0 02 F S ACCURACY 0 2 F S PHYSICAL OPERATING TEMERPATURE 32 104 F 0 40 C T4 WEIGHT 2 5 lbs 1 1 Kg PRO...

Страница 2: ... the media is hazardous classified the threaded exhaust port figure 1 should be vented into a safe area 5 Proceed with electrical connection TABLE 1 RATED PRESSURE FOR ISQB1 VALVES For valves ordered with MAX calibrated pressure of Max inlet pressure is Vacuum up to 10 psig 0 69 bar Consult factory 10 1 up to 30 psig 0 70 up to 2 bar 35 psig 2 4 bar 31 up to 100 psig 2 1 up to 7 bar 110 psig 7 6 b...

Страница 3: ...3 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 General Barrier ...

Страница 4: ...4 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS KFD2 ...

Страница 5: ...5 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS Z728 KFD2 ...

Страница 6: ...6 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PHEONIX CONTACT MACX ...

Страница 7: ...7 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS KFD0 ...

Страница 8: ...8 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS Z728 ...

Страница 9: ...ll Scale Pressure Type N 100 Pressure Ends Below Atmosphere P 100 Pressure Ends Above Atmosphere Z 100 Pressure Ends at Zero 10 Full Scale Pressure Must be less than or equal to 150 psig 12 Pressure Unit of Measure A Absolute Pressure G Gage Pressure 8 Zero Offset Pressure Typical is 0 blank If Greater than 30 of Full Scale Pressure 9 below Please Consult Factory Requires A for Pressure Unit of Me...

Страница 10: ...g to the section titled Electrical Connections 2 Connect a precision pressure gage or pressure transducer to the OUTLET PORT of the ISQB1 NOTE There must be a closed volume of at least 1 in3 between the OUTLET PORT and the measuring device for the ISQB1 to be stable 3 Provide supply pressure to the INLET PORT of the ISQB1 See figure 1 Make sure supply pressure does not exceed the rating for the va...

Страница 11: ...ges to equipment 1 PNEUMATIC CONNECTION All pipes pneumatic hose and tubing should be free of all contamination debris and chips prior to installation Flush pipes with compressed air to remove any loose particles 2 THREAD SEALANT To prevent product contamination thread tape is not recommended Instead a non migrating thread sealant is recommended for installation Apply sealant a couple threads from...

Отзывы: