1
ISQB1 Installation Guide - 2/13/2015 | SSS
DESCRIPTION / IDENTIFICATION
The ISQB1 series control valve is an electronic
pressure regulator designed to precisely and
proportionally control the pressure of gaseous media
based on an electronic control signal.
The ISQB1 operates using two normally closed
solenoid valves, a pressure sensor, and a control
circuit. One valve is actuated to allow supply media
into the system. The second valve is actuated to allow
working media to vent through a threaded port to
atmosphere. The pressure sensor provides feedback
to the control circuit. The control circuit compares the
pressure sensor feedback to the user supplied
electronic command signal and actuates the
appropriate valve until the two signals match.
The ISQB1 series can be teamed with a variety of air
piloted pressure volume boosters for even greater
flow.
†
Pressure ranges are customer specified. Output pressures other
than 100% are available.
ELECTRICAL
SUPPLY VOLTAGE 13.9 to 29 VDC (MAX)
SUPPLY CURRENT < 80 mA
COMMAND SIGNAL 4-20 mA Differential
COMMAND SIGNAL IMPEDANCE Current=100 Ω
MECHANICAL
PRESSURE RANGES Full Vacuum - 150 psig
(29.9 in. HG (Vac) - 10.3 Bar)
OUTPUT PRESSURE† 0-100% of range
FLOW RATE 0.80 SCFM @ 80 PSIG
(23 L/min @ 5.52 Bar)
Min CLOSED END VOLUME 1 in
3
PORT SIZE 1/8” NPT
FILTRATION RECOMMENDED 20 Micron
(included)
LINEARITY/HYSTERESIS <±0.15% F.S. BFSL
REPEATABILITY <±0.02% F.S.
ACCURACY <±0.2% F.S.
PHYSICAL
OPERATING TEMERPATURE 32-104°F
(0-40°C) (T4)
WEIGHT 2.5 lbs.
(1.1 Kg)
PROTECTION RATING NEMA 4
HOUSING Blue Anodized Aluminum
SPECIFICATIONS
HAZARDOUS AREA CLASSIFICATION
The ISQB is rated Intrinsically Safe and is
Factory Mutual approved for Class I, II &
III, Division 1, Groups C, D, E, F & G
Entity Parameters:
V Max = 29 VDC
I Max = 150 MA
Ci
= 0.26uF
Li
= 0
Field Wiring Drawing:
ISQB-96026-2
NOTES:
End user must determine fitness and
suitability of the ISQB1 control valve for their application.
The ISQB requires the use of Intrinsically Safe Barriers.
PROPORTION-AIR, INC.
8250 N. 600 West
McCordsville, IN 46055
877.331.1738
WETTED MATERIALS
PARAMTERS
Port 1 (Pressure Port)
Port 2 (Reference Port)
COVERS
High Temperature Polyamide
High Temperature Polyamide
SUBSTRATE
Alumina Ceramic
Alumina Ceramic
ADHESIVES
Epoxy, RTV
Epoxy, RTV
ELECTRONIC COMPONENTS
Ceramic, Silicon
Silicon, Glass, Gold, Solder
INSTALLATION & MAINTENANCE INSTRUCTIONS
Содержание ISQB1
Страница 3: ...3 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 General Barrier ...
Страница 4: ...4 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS KFD2 ...
Страница 5: ...5 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS Z728 KFD2 ...
Страница 6: ...6 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PHEONIX CONTACT MACX ...
Страница 7: ...7 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS KFD0 ...
Страница 8: ...8 ISQB1 Installation Guide 2 13 2015 SSS FIELD WIRING DRAWING ISQB 96026 2 PEPPERL FUCHS Z728 ...