![ProMinent ProMix C Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/prominent/promix-c/promix-c_operating-instructions-manual_1616984028.webp)
Pr
o
Minent ProMix
‘S & C’ Polymer Feeder
ProMix Series S&C User Manual
2.10 Response on Loss of 4-20 mA Input
Press
ENTER
at 4-20mA input.
Press
UP
or
DOWN
to
lin Fail State
.
Displays the factory default.
Pump OFF
when
4-20mA Input
less than 4mA.
Press
ENTER
to select a different response.
Press
DOWN
to select a user set pump
speed on less than 4 mA.
Displays the factory default of 10%.
Press
ENTER
to select response & modify value.
Press
DOWN and ENTER
to run the pump at the last input
Value greater than 4.0mA when the measured current loop
value falls below 4.0mA.
.
If you pressed
ENTER
@
Pump @ 10%
You will be able to modify the
10%
value.
Press
RIGHT
to move the underline cursor &
UP
or
DOWN
to modify the value at the cursor.
Press
EXIT
to leave unchanged or
ENTER
To set the new value.
Sidebar:
The feeder defines a failed 4-20mA input @ -1% which is nominally 3.85mA.
(4.0mA
– 0.01 x 16.0mA = 3.84mA)
3.85mA allows 4.0mA, a valid pump control signal some headroom prior to a fault response
Содержание ProMix C
Страница 44: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual General Mechanical Layout ProMix C DA...
Страница 46: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual P N 7747255 Mixing Chamber Components...
Страница 50: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual B 2 Control Panel Drawings...
Страница 51: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Страница 52: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Страница 53: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Страница 54: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...
Страница 55: ...ProMinent ProMix S C Polymer Feeder ProMix Series S C User Manual...