Metering

monitor

19

BYTE

If a metering monitor is installed, it can be switched on (1).

Deactivation is (0).

Concentra‐

tion

20

FLOAT

If the concentration calculation is activated on the pump, the

current concentration can be read off here (delta

®

 only).

Error

21

UINT16

bit

Name

Function

 

 

 

0

Minimum

Metering liquid level too low

 

 

 

1

Batch

Too many metering strokes >

100000

 

 

 

2

 

Analogue current is less than

4 mA

 

 

 

3

Analogue >

23mA

Analogue current is greater

than 23 mA

 

 

 

4

Metering

monitor

Metering monitor fault

 

 

 

5

Diaphragm

rupture

Faulty diaphragm in the

dosing head

 

 

 

6

Airlock

Air in the dosing head (delta

®

only)

 

 

 

7

Overpressure Overpressure in the

hydraulic system

 

 

 

8

-

-

 

 

 

9

-

-

 

 

 

10

Low pressure Pressure too low in the

hydraulic system (delta

®

only)

 

 

 

11

Stroke length

changes

The stroke length was

changed in locked state.

 

 

 

12

Bleeding

Automatic bleeding is not

possible (delta

®

 only)

 

 

 

13

Bus error

Bus error reported by the

module

 

 

 

14

System error System components faulty -

see LCD screen

 

 

 

15

Module error Fault in module handling

Warnings

22

UINT16

bit

Name

Function

 

 

 

0

Minimum

Metering liquid level too low

 

 

 

1

Calibration

Stroke length set outside the

calibration tolerance

 

 

 

2

Metering

monitor

Metering monitor fault

 

 

 

3

Diaphragm

rupture

Faulty diaphragm in the

dosing head

 

 

 

4

Airlock

Air in the dosing head

 

 

 

5

-

-

 

 

 

6

-

-

Operation

 

 

 

14

Содержание DULCOnvert

Страница 1: ...th controlled solenoid drive optoDrive DLTa or the Operating instructions for the motor driven metering pump Sigma x Control type SxCb EN 982920 BA PM 008 02 18 EN Please carefully read these operatin...

Страница 2: ...e PROFIBUS mode 7 3 1 General 7 3 2 Displays 7 3 3 LEDs on the PROFIBUS module 8 3 4 Using the metering monitor 8 4 Assembly and electrical installation 9 5 Operation 11 5 1 General 11 5 2 GSDML File...

Страница 3: ...n appears in the operating menu The pump requires a minimum of software version V01 03 06 00 delta DLTa or V01 01 00 00 Sigma Control SxCb and hardware version V01 04 00 00 for the delta for the PROFI...

Страница 4: ...PROFIBUS cable to the pump s PROFIBUS socket 2 Press P for 2 seconds on the pump 3 delta only Use the arrow keys to go to Settings and press P 4 Use the arrow keys to go to PROFIBUS and press P 5 Use...

Страница 5: ...ia the PROFIBUS to the master PLC Programmable Logic Controller PC etc If the PROFIBUS is set to inactive the settings for the operating mode previously selected are reloaded If the pump is switched t...

Страница 6: ...4 Assign a new name via Online diagnostics Fig 2 5 Continue configuring as usual Description of the available objects refer to Operation chapter Setting up installation 6...

Страница 7: ...mp is switched to PROFIBUS mode it stops and can only be restarted using the PROFIBUS 3 2 Displays There are other identifiers in the operating display when PRO FIBUS mode is running The current ident...

Страница 8: ...o connection to the PROFIBUS Lit green Pump in cyclic mode 3 4 Using the metering monitor The Metering monitor socket must be used to use the metering monitor in PROFIBUS mode The pump then transmits...

Страница 9: ...Onvert to the pump s PROFIBUS socket There is no need for terminal resistors Connect the plug in power unit of the DULCOnvert to the mains voltage 1 Unscrew the housing screws and open the cover 2 Scr...

Страница 10: ...urfaces of the housing cover and the black seal of the lower part of the housing are free of dirt 2 Replace the housing cover onto the lower part of the housing and fasten in place with the screws 3 C...

Страница 11: ...pump can participate in cyclic data transfer Only standard parameterisation is needed for this there are no application specific parameters Please note Data is stored according to the Big Endian prin...

Страница 12: ...emory is activated 15 Calibrated Pump is calibrated 16 Relay 1 Relay 1 is physically present 17 Relay 2 Relay 2 is physically present 18 AnalogOut Module is physically present 19 Diaphragm rupture Dia...

Страница 13: ...ing frequency in strokes hour 0 12000 The maximum frequency can be significantly lower than in normal mode according to the metering mode set Batch prese lection 10 11 UINT32 Number of strokes in batc...

Страница 14: ...m in the dosing head 6 Airlock Air in the dosing head delta only 7 Overpressure Overpressure in the hydraulic system 8 9 10 Low pressure Pressure too low in the hydraulic system delta only 11 Stroke l...

Страница 15: ...a transmission in the PROFIBUS 5 4 1 Overview of the data objects The data objects are summarised into modules and their configura tion identifier see following table The configuration identifier allo...

Страница 16: ...counter 1 byte Stroke counter 4 bytes Stroke number C0 80 83 14 Delete quan tity counter 1 byte Volume counter Litres per stroke 4 bytes 4 bytes Quantity C0 80 87 Tab 3 Pump data output data Offset Va...

Страница 17: ...7 8 high low UINT16 Actual fre quency 0 max freq 9 10 high low UINT16 Maximum fre quency 0 12000 Maximum fre quency 5 11 12 13 14 high low UINT32 Batch prese lection 1 99999 Batching 6 15 16 17 18 hi...

Страница 18: ...order If the data of a module is not to be involved in cyclic data transmission then an empty module must be config ured at this point 5 5 Extended diagnostics from the 7th byte The pump uses the mech...

Страница 19: ...ss 3rd byte No see Table 2 0x30 OK 0x31 Date outside of limits 0x32 Date protected 0x34 Option not installed 0x35 Service not defined 0x36 Value cannot be changed 0x37 Update completed 0x55 Communicat...

Страница 20: ...C Degree of protection IP66 with professional installation PROFIBUS cable length 2 m Plug in power unit length 1 5 m Housing HxWxD 140x110x60 mm without threaded connectors Electrical data Degree of p...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...982920 1 en_GB 2017 ProMinent GmbH Im Schuhmachergewann 5 11 69123 Heidelberg Germany Germany Telephone 49 6221 842 0 Fax 49 6221 842 419 Email info prominent com Internet www prominent com...

Отзывы: