Installation of the F module
The F module uses the installation space of the A and P modules.
The existing functions in the combination of A and P modules are
covered by the F module. To control the hygiene parameters, an M
module is always required. The sensors for pH, redox, temperature
and sample water flow monitoring are connected to the M module.
You can also connect the external DIN contact to the M module.
+ - + -
out1 out2
90 - 253 VAC
XA 1
XK 1
XK 2
XK 3
XR 1
XR 2
XR 3
XR 4
XR 5
XR 6
XR 7
XP 1
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3 L N PE
+ - + -
Digital_IN
+ - + -
Digital_IN
+ -
+
-
Digital_IN
P_REL 1
Alarm
L* N PE
P_REL 2
L* N PE
P_REL 3
L* N PE
P_REL 4
L* N PE
P_REL 5
L* N PE
P_REL 6
L* N PE
P_REL 7
Com
NO
NC
K1
K3
K5
K2
K4
0/4...20 mA
A1254
Fig. 1: Terminal allocation F-module
2.1 Naming of the mA outputs
Number
Description
Function
Iout1
free
Free. Not used
Iout1
CntrlCirc1
Control variable, circulation (circulating pump, filtration circuit 1)
Iout2
free
Free. Not used
Iout2
CntrlCirc2
Control variable, circulation (circulating pump, filtration circuit 2)
Iout2
CntrlChlorination
↑
Control variable, raise chlorine dosing
Iout2
Cntrl.pH_increase
Control variable, raise pH value
Iout2
Cntrl.pH_reduce
Control variable, reduce pH value
2.2 Naming of the PCB digital inputs
Number
Description
Function
K1 ... K5
free
No function, not assigned.
K3
Liquid level
For 1-stage level control, liquid level low = filling starts for x
Chapter 5.6 ‘"Water level control"’ on page 21.
K2
Low flow
contact--
for 4-stage level control. Raw water tank = liquid level low fault.
Circulation stops. See
Chapter 5.6 ‘"Water level control"’
K3
Level min-
for 4-stage level control. Raw water tank = liquid level low, filling
starts. See
Chapter 5.6 ‘"Water level control"’ on page 21.
K4
Level max+
for 4-stage level control. Raw water tank = full. Filling stops. See
Chapter 5.6 ‘"Water level control"’ on page 21.
K1, K5
Level ++ Alarm
for 3-stage level control. Raw water tank = overfull. Filling stops,
alarm relay switches. See
Chapter 5.6 ‘"Water level control"’
K1 ... K2
Water meter
Connection for contact water meter for recording the fresh water
top-up volume. See
Chapter 5.6 ‘"Water level control"’
Installation of the F module
5