8
Technical data
8.1 Ambient conditions
Description
Value
Working temperature:
- 10 °C ... + 45 °C
Storage temperature:
- 20 °C ... + 85 °C
Air humidity:
max. 95 % (non-condensing)
Air pressure:
max. 2000 m (above sea level)
8.2 Mechanical data
Description
Value
Weight:
approx. 525 g
Dimension (WxLxH):
approx. 218x172x42 mm
8.3 Electrical data
Mains voltage: 90-254 V AC 50/60 Hz. Created at terminal XP1.
Current consumption Dependent on the connected loads. The
independent requirement of the electronics is max. 30 W. During
operation no more than insignificant spikes are to be expected.
Terminal strip XP1-Pin
Signal
Function
1
L
Phase
2
N
Neutral conductor
3
PE
Protective earth conductor
On-board fuses
n
F2: 0.63 ampere, slow-acting, (in fuse holder F1) for the elec‐
tronics - internal unit (F module)
n
F4: 10 ampere, slow-acting, (in fuse holder F3) for the switched
outputs XR2 (relay K2), XR3 (relay K3), XR6 (relay K6).
– Maximum load: 8 amperes, due to a possible ambient tem‐
perature of up to 45 °C
n
F6: 10 ampere, slow-acting, (in fuse holder F5) for the switched
outputs XR4 (relay K4), XR5 (relay K5), XR7 (relay K7).
– Maximum load: 8 amperes, due to a possible ambient tem‐
perature of up to 45 °C
Power supply (at XP1)
Fuses
Technical data
32