Example IN1L and IN1H settings:
If a 4-20mA sensor is selected as IN1, the sensor LOW value (SL) is 4mA, the sensor
HIGH value (SH) is 20mA. The input signal looks like this:
Input for linear sensors
Process value
Input signal
Formula:
𝑃𝑉1 = 𝐼𝑁1𝐿 + (𝐼𝑁1𝐻 − 𝑁𝐼1𝐿) ∗
𝑆−𝑆𝐿
𝑆𝐻−𝑆
Example:
Pressure transmitter with the range of 0 - 15 bar is connected to input 1,
with 4-20mA
Output signal connected. Please make the following settings:
IN1 = 4 - 20 IN1L = 0.0
IN1U = PU IN1H = 15.0
DP1 = 1-DP
To change the resolution, you can also make other settings at DP1.
6.2 output 1 and 2 (OUT1 / OUT2)
O1TY: Select the output signal for output 1 (OUT1)
The selection must match the installed module (see type code)
Possible output signals are:
RELY: Switching output relay (type
–A)
SSRD: Pulsed voltage output as SSR driver (type -C)
SSR: Switching output for controlling SSR relays (in planning)
4 - 20: 4 - 20 mA Current output (type
–B)
0 - 20: 0 - 20 mA Current output (type
–B)
0 - 1 V: 0 - 1 V Voltage output (in planning)
0 - 5 V: 0 - 5 V Voltage output (in planning)
1 - 5 V: 1 - 5 V Voltage output (in planning)
0 - 10V: 0 - 10 V Voltage output (in planning)
O2TY: Select the output signal for output 2 (OUT2)
The selection must match the installed module (see type code)
Same selection options as output 1 (O1TY).