Base
Function
Parameter
Name
Display
Parameter
describtion
Range
Standard
Value
No
IN2
IN2 Sensor type
0 : IN2 deactivated
1 : Current transformer
2 : 4...20mA linear
3 : 0...20mA linear
4 : 0...1VDC linear
5 : 0...5VDC linear
6 : 1...5VDC linear
7 : 0...10VDC linear
1
No
IN2U
IN2 unit
see IN1
2
No
DP2
IN2 Decimal point
see IN1
1
No
IN2L
IN2 LOW-scaling
Low: -19999 High: 45536
0
No
IN2H
IN2 HIGH-scaling
Low: -19999 High: 45536
1000
Yes
OUT1
output 1 fuction
(OUT1)
0 : Heating (opposite)
1 : Cooling (direct)
0
Yes
O1TY
OUT1 Signal type
0 : Relay
1 : SSR Driver
2 : SSR Relay
3 : 4…20mA module
4 : 0…20mA module
5 : 0…1VDC module
6 : 0...5VDC module
7 : 1...5VDC module
8 : 0...10VDC module
0
Yes
CYC1
OUT1 cycle time
Low: 0,1 High: 100,0sec.
18
Yes
O1FT
OUT1 Error behavior
BPLS for bumpless transfer or 0,0…100,0% as default value for
OUT1 in case of error, when switching on or activating the
manual mode
BPSL
Yes
OUT2
output 2 function
(OUT2)
0 : OUT1 deactivate
1 : PID cooling
2 : DC Sensor supply installed
0
Yes
O2TY
OUT2 Signal type
see O1TY
0
Yes
OYC2
OUT2 Cycle time
Low: 0,1 High: 100,0sec.
18
Yes
O2FT
OUT2 Error behavior
BPLS for bumpless transfer or 0,0…100,0% as default value for
OUT2 in case of error, when switching on or activating the
manual mode
BPSL
Yes
A1FN
Alarm 1 function
0 : No alarm function
1 : Timer action
2 : Difference high alarm
3 : Difference low alarm
4 : Difference band deviation alarm
5 : Difference band alarm
6 : IN1 Process value high alarm
7 : IN1 Process value low alarm
8 : IN2 Process value high alarm
9 : IN2 Process value low alarm
10 : IN1 or IN2 high alarm
11 : IN1 or IN2 low alarm
12 : IN1-IN2 high Difference alarm
13 : IN1-IN2 low Difference alarm
14 : Control loop alarm
15 : Sensor break or A-D error
2
Yes
A1MD
Alarm 1 Mode
0 : Normal alarm mode
1 : Storing alarm
2 : Alarm held
3 : Storing & held alarm
0
Setup
Menu