Included
in
Base
function
Parameter
Name
Display
Parameter
describtion
Range
Standard
Value
Yes
A1FT
Alarm 1 Error behavior
0 : Alarm output OFF in case of error
1 : Alarm output ON in case of error
1
Yes
A2FN
Alarm 2 function
See alarm 1 function
2
Yes
A2MD
Alarm 2 mode
See alarm 1 mode
0
Yes
A2FT
Alarm 2 Error behavior
See alarm 1 Error behavior
1
No
EIFN
Event input function
0 : No event function
1 : SP2 replaces SP1
2 : PB2, TI2, TD2 replaces PB1, TI1, TD1
3 : SP2, PB2, TI2, TD2 replaces SP1, PB1,
TI1, TD1
4 : Reset alarm output 1
5 : Reset alarm output 2
6 : Reset alarm 1 & 2
7 : Output 1 deactivate
8 : Output 2 deactivate
9 : Output 1 & 2 deactivate
10 : Lock all parameters
1
No
PVMD
PV Mode selection
0 : PV1 as process value
1 : PV2 as process value
2 : PV1 - 2 as process value
3 : PV2 - 1 as process value
0
No
FILT
Damping filter for PV
0 : 0 Seconds
1 : 0,2 Seconds
2 : 0,5 Seconds
3 : 1 Seconds
4 : 2 Seconds
5 : 5 Seconds
6 : 10 Seconds
7 : 20 Seconds
8 : 30 Seconds
9 : 60 Seconds
2
yes
SELF
Self-optimization
0 : deactivate
1 : activate
0
Yes
SLEP
Sleep mode
0 : deactivate
1 : activate
0
No
SPMD
Set point mode
0 : SP1 or SP2 as setpoint ( depending
on EIFN-setting
1 : Minute ramp as setpoint
2 : Hour ramp as setpoint
3 : IN1 as set point
4 : IN2 as set point
5 : Selection for pump control
0
Yes
SP1L
SP1 LOW-Value
Low: -19999 High: 45536
0 °C
Yes
SP1H
SP1 HIGH-Value
Low: -19999 High: 45536
1000 °C
No
SP2F
Setpoint 2 format
0 : SP2 is a direct value
1 : SP2 is a difference value
0
s
etup
Menu