background image

27 

 

 

4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm in the front 

display panel even though the mains is 

normal.   

The AC input power is not 

connected well. 

Check if input cable  firmly 

connected to the mains.   

The icon 

and the warning code 

  flash on LCD display and alarm 

beeps every second. 

EPO function is enabled. 

Set the circuit in closed 

position  to disable EPO 

function.   

The icon 

and 

  flash on 

LCD display and alarm beeps  every 

second. 

The external or internal 

battery is incorrectly 

connected. 

Check if all batteries are 

connected well. 

The icon 

  and

  flash on 

LCD display and alarm beeps twice 

every second. 

UPS is overload.   

Remove excess loads from UPS 

output. 

UPS is overloaded. Devices 

connected to the UPS are fed 

directly by the electrical 

network via the Bypass. 

Remove excess loads from UPS 

output. 

After repetitive overloads, the 

UPS is locked in the Bypass 

mode. Connected devices are 

fed directly by the mains. 

Remove excess loads from UPS 

output first. Then shut down 

the UPS and restart it. 

Fault code is shown as 43. The icon 

  lights on LCD display and 

alarm beeps continuously. 

UPS is overload too long and 

becomes fault. Then UPS shut 

down automatically. 

Remove excess loads from UPS 

output and restart it. 

Fault code is shown as 14, the icon 

  lights on LCD display, and 

alarm beeps continuously. 

The UPS shut down 

automatically because short 

circuit occurs on the UPS 

output. 

Check output wiring and if 

connected devices are in short 

circuit status. 

Fault code is shown as 01, 02, 03, 04, 

11, 12, 13, 14,1A, 21, 24, 36, 41, 42 or 

43  on LCD display and alarm beeps 

continuously. 

A UPS internal fault has 

occurred. There are two 

possible results: 

1. The load is still supplied, but 

directly from AC power via 

bypass.   

2. The load is no longer 

supplied by power.   

Contact your dealer. 

Battery backup time is shorter than 

nominal value 

Batteries are not fully charged 

Charge the batteries for at 

least  7  hours and then check 

capacity. If the problem still 

persists, consult your dealer.   

Batteries defect 

Contact your dealer to replace 

the battery. 

The icon 

and 

  flash on LCD 

display and alarm beeps every second. 

Fan is locked or not working; 

or the UPS temperature is too 

high. 

Check fans and notify dealer.   

 

Содержание 10KRT

Страница 1: ...ONLINE UPS User Manual MASTER II SERIES 1P 1P RACK TOWER PRO800 QRS QRL 6KVA 10KVA Version 1 00 English...

Страница 2: ...LE UPS INSTALLATION 7 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 6 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION 12 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGL...

Страница 3: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Страница 4: ...ed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary power switches installed in places away from the device to alert the electrical mainte...

Страница 5: ...its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fu...

Страница 6: ...owing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option On...

Страница 7: ...available for parallel model 3 External battery connector 4 Intelligent slot 5 RS 232 communication port 6 USB communication port 7 Emergency power off function connector EPO connector 8 Input circuit...

Страница 8: ...module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 S...

Страница 9: ...c shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and d...

Страница 10: ...ld only connect to its supplied external battery pack The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for l...

Страница 11: ...or Parallel System If the UPS is only available for single operation you may skip this section to the next 1 Install and wires the UPSs according to the section 2 3 2 Connect the output wires of each...

Страница 12: ...10 Diagram 2 Wiring diagram of parallel system for tower model Diagram 3 Power cable connection for RT model Diagram 4 Wiring diagram of parallel system for RT model...

Страница 13: ...11 2 6 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown...

Страница 14: ...s button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press...

Страница 15: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Страница 16: ...operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the input breaker In Bypa...

Страница 17: ...up time may be shorter than expected time 3 4 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more th...

Страница 18: ...it means that there are some problems for UPS operation Users can get the warning code from LCD panel Please check the 3 11 warning code table and the trouble shooting table in chapter 4 for details...

Страница 19: ...e error between real output voltage and detected value of UPS is less than 1V 3 Turn off each UPS Refer to section 3 4 7 Then follow the wiring procedure in section 2 4 4 Remove the cover of parallel...

Страница 20: ...le Then remove the unit from the parallel system Second method 1 If the bypass is abnormal you can not remove the UPS without interruption You must cut off the load and shut down the system 2 Make sur...

Страница 21: ...to set up the UPS Refer to following diagram Programs available list for parameter 1 Code Description Bypass No output AC ECO CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Vol...

Страница 22: ...60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will...

Страница 23: ...range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS disab...

Страница 24: ...ng Interface Setting Parameter 3 000 999 Set the maximum backup time from 0min to 999min UPS will shut down to protect battery after backup time arrives DIS Disable battery discharge protection and ba...

Страница 25: ...ld be suitable to battery specifications 15 Inverter voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6...

Страница 26: ...se set up calibrated current as 3 Setting charging current 4A real measured current 3 7A 0 3A 3 8 Operating Mode Status Description If parallel UPS systems are successfully set up it will show one mor...

Страница 27: ...lay Bypass mode Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test De...

Страница 28: ...PS 12V abnormal 6E None 3 10 Warning Indicator Warning Icon flashing Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Bee...

Страница 29: ...ads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then UP...

Страница 30: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Страница 31: ...A 10 max 4 A 10 max 1 A 10 max 4 A 10 max Charging Voltage Battery number 13 65 V 1 PHYSICAL Dimension DXWXH mm UPS Unit 600 x 438 x 88 2U Battery Pack 688 x 438 x 88 2U UPS Unit 600 x 438 x 88 2U UPS...

Страница 32: ...ERS INDONESIA Office PT PROLiNK INTIDATA NUSANTARA Walk In Jl Cideng Barat No 79 Jakarta Pusat 10150 Indonesia Email Support support id prolink2u com MALAYSIA Office FIDA SYSTEMS M SDN BHD Walk In 29...

Отзывы: