background image

Technical data

Installation

Cat.: see nameplate on cover; Class 3

Type “X” hobs

EQUIPMENT

For the LAYOUT OF HOTPLATES see 

figure 1

at the back of this ma

nual.

INSTALLATION

The installation, adjustments, conversions and
maintenance operations listed in this part must
only be carried out by qualified personnel. The
manufacturer cannot be held responsible for any
damage to persons or property resulting from an
incorrect installation of the appliance.
The safety and automatic adjustment devices of
the appliance may, during its life, only be modi-
fied by the manufacturer.
The hob must be installed by a qualified person
in accordance with the Gas Safety (Installation
and use) (Amendment) Regulations 1990 and
the relevant building / I.E.E.
Failure to install the appliance correctly could in-
validate any manufacturers warranty and lead to
prosecution under the above quoted regulation.
The following British Standards should be used
as reference when installing this appliance:
BS6172 1990, BS5440 part 2 1989 and BS6891
1988.
In the UK C.O.R.G.I. registered installers are au-
thorised to undertake the installation and service
work  in compliance with the above regulations.
All Comet authorised installers are C.O.R.G.I.
registered.
Before installation, make sure that local distribu-
tion conditions (gas and electrical) are compati-
ble with the appliance's adjustment.
As it is not connected to a device for the evacua-
tion of the products of combustion, it must be in-
stalled in accordance with the current regulations
and used in a well ventilated location.
Particular attention must be paid to the regula-
tions on ventilation.

VENTILATION

All rooms require an openable window or equiva-
lent, while some rooms require a permanent vent
in addition to the openable window.
The appliance should not be installed in a room
of volume less than 6m

3

 (for instance say

3

GAS

Burner

Injector

Consumption

low flow-rate

nominal flow-rate

(kW)

(kW)

G20

auxiliary

76

95 l/h

0,45

1,00

20

semi-rapid

94

157 l/h

0,60

1,65

mbar

rapid

128

276 l/h

0,95

2,90

G30/G31

auxiliary

50

73 g/h

0,45

1,00

28-30 mbar

semi-rapid

65

120 g/h

0,60

1,65

37 mbar

rapid

85

211 g/h

0,95

2,90

GAS BURNERS CHARACTERISTICS

Содержание TCG40IX

Страница 1: ...Proline GAS HOB Model TCG40IX Instruction Book...

Страница 2: ...Operating and Installation Instructions GB...

Страница 3: ...in a safe place for future reference The installation and maintenance operations list ed must only be carried out by qualified person nel The appliance must only be used for its original purpose that...

Страница 4: ...5440 part 2 1989 and BS6891 1988 In the UK C O R G I registered installers are au thorised to undertake the installation and service work in compliance with the above regulations All Comet authorised...

Страница 5: ...there is a wall unit or hood above the hob there must be at least 750mm between the hob and the unit or hood If the hob is not installed over a built in oven it is essential to install a heat baffle...

Страница 6: ...injectors after replacing check that all the injectors are airtight SETTING HOB BURNER MINIMUM LEVELS If the hob is to work on bottled gas butane propane the tap by pass must be screwed right down Th...

Страница 7: ...obstructed or install an extractor hood with fan In case of intensive or prolonged use additional ventilation may be required open a window or in crease the extractor fan power IGNITING THE HOB BURNER...

Страница 8: ...tly Keep the electrodes clean so that the sparks always strike Note To avoid damage to the electric ignition do not use it when the burners are not in place Control knobs The control knobs can be remo...

Страница 9: ...8 Figure A AUXILIARY SR SEMIRAPID R RAPID 1 2 3 4...

Страница 10: ...9 Figure 9 5 6 7 8...

Страница 11: ......

Страница 12: ......

Страница 13: ...ED 12 09 2003 334995...

Отзывы: