Proline Promag L 400
10
Hauser
EtherNet/IP
Standards
In accordance with IEEE 802.3
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode
Selectable (as per NAMUR recommendation NE 43):
• Minimum value: 3.6 mA
• Maximum value: 22 mA
• Defined value: 3.59 to 22.5 mA
• Actual value
• Last valid value
0-20 mA
Failure mode
Choose from:
• Maximum alarm:22 mA
• Defined value: 0 to 22.5 mA
HART
Device diagnostics
Device condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure mode
Choose from:
• Actual value
• No pulses
Frequency output
Failure mode
Choose from:
• Actual value
• Defined value: 0 to 12
500 Hz
• 0 Hz
Switch output
Failure mode
Choose from:
• Current status
• Open
• Closed
EtherNet/IP
Device diagnostics
Device condition can be read out in Input Assembly
Local display
Plain text display
With information on cause and remedial measures
Backlight
Red backlighting indicates a device error.
Status signal as per NAMUR recommendation NE 107