When starting up each one of the modules, the STATUS LED on the front of each module will 

flash for a few seconds with a short but constant flash, indicating that other elements (masters, 
slaves) are being searched within the network. With the connection already established, the LED 
will flash by emitting groups of flashes, the number of which will depend on the power of the 
received signal. This number of flashes can vary between two and seven:

• 

Two flashes: correspond to the minimum usable power.

• 

Seven flashes: correspond to the maximum signal available.

If the radio connection is interrupted, the flashes will return to constant short flashes.

Each module has three additional status LEDs at the bottom:

• 

Yellow LED

: Steady indicates communication is established

• 

Green LED

: It will turn on whenever there is an active input

• 

Red LED

: It will turn on whenever there is an active output

LEDs 

Inputs

: The inputs are located at the bottom of the module and are numbered 

D1 to D6.

 To 

activate a specific input, it must go to a high logic state: the inputs are 

active

 and there must be 

a voltage level (5 - 30 V) on the + pin of the corresponding input. The pin immediately to the right 
of each input (shown as -) must be connected to earth.

When an input is activated, the corresponding relay in the reciprocal module is activated. The 

green LED

 on the module where the input is activated and the 

red LED

 on the module where the 

output is activated will also be activated.

Inputs, outputs and antenna

Содержание Radiocontrol 6i-6o

Страница 1: ...eans that each individual unit is a transmitter and receiver at the same time so that eventually the remote equipment to which orders are sent can also send the status of its inputs The signals are tr...

Страница 2: ...red from the factory to operate in two different modes Standard mode has a minimum of two modules and a maximum of seven modules Now in all cases there will only be one master and the rest of the modu...

Страница 3: ...le master slave pairs although in this case the four masters use a single antenna and are interconnected via cable RS485 In this way the operation is much more optimal at the radio electric level sinc...

Страница 4: ...Slave In standby 28 40 Communicating 1 sec 70 100 Output power 500 mW Frequency range 169 4000 169 8125 MHz Channels 16 Channel spacing 25 kHz Maximum communication distance according to orography Om...

Страница 5: ...each frame received from the master module with the status of its inputs and is reproduced on the outputs of the master module according to the established input output mapping There can be two securi...

Страница 6: ...onstant short flashes Each module has three additional status LEDs at the bottom Yellow LED Steady indicates communication is established Green LED It will turn on whenever there is an active input Re...

Страница 7: ...ctivated To facilitate the passage of the hose from the inputs and outputs of each module to the devices to be activated three cable glands have been placed in the boxes Antenna The standard system is...

Страница 8: ...ave radio control where a digital sensor is connected to the radio control located in the reservoir which when insufficient water is detected contact closes sends an order to the radio control located...

Отзывы: