The system can operate in standard mode or multi-master mode. The operating mode and 

mapping of the inputs/outputs of the different modules in the system must be detailed when 
placing the order, as it is configured in the factory.

The master device (or multimaster) will attempt to establish contact with the slave modules 

from its connection to the network. To do this, it will be sending interrogation frames until it 
receives a response from all the slaves. This interrogation will be:

Once the automatic link between the master module and the slaves has been made, the master 

will send a refresh frame according to the set time interval of 1 second. Also, and immediate-
ly when there is a change in the inputs of the master module, its status to each of the slave 
modules and each of these will reproduce it on their outputs. Each slave module replies to each 
frame received from the master module with the status of its inputs and is reproduced on the 
outputs of the master module according to the established input/output mapping.

There can be two security settings in case of radio communication interruption:

• 

Secure mode

: (mode set by default), if the radio communication is interrupted, the 

remote relays go to inactive status (open). It is determined that the communication has 
been interrupted when 90" have passed without information exchange between master(s) 
and slaves.

• 

Persistent mode

: the relays will not change their status if a radio link is cut.

The master(s) is the element of the system that is responsible for supervising the system, pe-

riodically interrogating the slaves. If communication is interrupted, the contact on the output 
marked as 

ALARM

 will open. The contact remains closed when the communication is correct. 

On the slave, this output has no functionality.

Operation

Multimaster mode

1 master

Every 1 second

2 masters

Every 2 seconds

3 masters

Every 3 seconds

4 masters

Every 4 seconds

Same 
mode

Standard mode

Every 1 second

Содержание Radiocontrol 6i-6o

Страница 1: ...eans that each individual unit is a transmitter and receiver at the same time so that eventually the remote equipment to which orders are sent can also send the status of its inputs The signals are tr...

Страница 2: ...red from the factory to operate in two different modes Standard mode has a minimum of two modules and a maximum of seven modules Now in all cases there will only be one master and the rest of the modu...

Страница 3: ...le master slave pairs although in this case the four masters use a single antenna and are interconnected via cable RS485 In this way the operation is much more optimal at the radio electric level sinc...

Страница 4: ...Slave In standby 28 40 Communicating 1 sec 70 100 Output power 500 mW Frequency range 169 4000 169 8125 MHz Channels 16 Channel spacing 25 kHz Maximum communication distance according to orography Om...

Страница 5: ...each frame received from the master module with the status of its inputs and is reproduced on the outputs of the master module according to the established input output mapping There can be two securi...

Страница 6: ...onstant short flashes Each module has three additional status LEDs at the bottom Yellow LED Steady indicates communication is established Green LED It will turn on whenever there is an active input Re...

Страница 7: ...ctivated To facilitate the passage of the hose from the inputs and outputs of each module to the devices to be activated three cable glands have been placed in the boxes Antenna The standard system is...

Страница 8: ...ave radio control where a digital sensor is connected to the radio control located in the reservoir which when insufficient water is detected contact closes sends an order to the radio control located...

Отзывы: