USER INTERFACE
26
Screen for displaying/setting the parameters
An example of visual for displaying/setting the parameters is shown in the figure, also
highlighting the fields and icons used:
1.
Parameters
2.
Screen identifier
3.
Menu
The display identifier details the menu branch and the mask: the first character indicates the
menu branch, while the two alphanumeric digits identify the order of the mask inside the
menu. For example mask Bab01 is the first mask in menu B.a.b
Paramètres de consigne (valeurs données à titre indicatif)
*Min. Speed MT50 : 45 rps. Min. Speed parallel compressor on LT versions : 25 rps
Risk of condensation if the CO
2
pressure receiver is below 55 Bar (on MT unit)
Label
Description
Unit
Min
Max
Setpoint
MT
LT
Cab03
Compressor pressure
barg
10.0
40.0
26.5
13.0
Cae24
Suction high pressure alarm threshold (absolute)
barg
60.0
Cae26
Suction low pressure alarm threshold (absolute)
barg
10.0
5.5
Caf17
Minimum on time compressor
s
0
999
120
Caf17
Minimum off time compressor
s
0
999
180
Caf17
Minimum time to start same compressor
s
0
999
310
Cag52
Max speed
rps
0.0
999.9
100.0
Cag52
Min speed
rps
0.0
99.9
25.0*
45.0*
Dab03
Gascooler setpoint
°C
12.0
38.0
22.0
Dae06
High gas cooler pressure alarm threshold
barg
0.0
6553.
5
120.0
Dae07
Low gas cooler pressure alarm threshold
barg
0.0
6553.
5
32.0
Phb28
Maximum HPV safety setpoint
barg
10.0
120.0
90.0
Phb28
Minimum HPV setpoint
barg
-1.0
150.0
40.0
Fhb22
Regulation – CO
2
receiver pressure setpoint
barg
0.0
150.0
55.0 (MT) 35.0 (LT)
Содержание QC LT
Страница 24: ...REFRIGERANT CIRCUIT DIAGRAM 21 QUIETCO2OL AIR COOLED MT Version LT Version ...
Страница 25: ...REFRIGERANT CIRCUIT DIAGRAM 22 QUIETCO2OL WATER COOLED VERSION MT Version LT Version ...
Страница 30: ...USER INTERFACE 27 Navigation To navigate inside the menu tree use the following buttons ...
Страница 36: ......
Страница 43: ...APPENDIX 1 REFRIGERANT AND OIL CHARGE AIR COOLED VERSION 39 ...
Страница 44: ...APPENDIX 1 REFRIGERANT AND OIL CHARGE AIR COOLED VERSION 40 ...