REFRIGERANT PIPING WORK
15
Selection of Refrigerant Piping Size
The connection piping size for refrigeration unit is, in principle, as shown
below, but each installation should be determined by calculating pressure loss
of the piping and refrigerant flow speed and making sure no problem occurs in
the cooling capacity and oil return.
As refrigeration unit using CO2 refrigerant incurs pressure higher than when
using traditional refrigerants, it is necessary to choose adequate materials.
Make sure that piping’s are connected to the appropriate pressurized
equipment (EN378-2).
Product
Suction line
(R744)
Liquid line
(R744)
PS
MT30
9,52 mm (3/8")
9,52 mm (3/8")
80 bars
MT50
9,52 mm (3/8")
9,52 mm (3/8")
80 bars
MT67
9,52 mm (3/8")
9,52 mm (3/8")
80 bars
MT100
9,52 mm (3/8")
9,52 mm (3/8")
80 bars
LT75
9,52 mm (3/8")
9,52 mm (3/8")
80 bars
LT167
12,7 mm (1/2")
9,52 mm (3/8")
80 bars
Prevent contamination of foreign objects
such as dust, metal powder, oxide scale, etc.
Since the compressor consists of high precision components, contaminants
generate scratches on the sliding surfaces, thereby increasing gas leak,
deteriorating performance, and causing excessive wear and seizure.
–
Flow nitrogen gas during welding.
–
Piping inside and outside must be clean.
Содержание QC LT
Страница 24: ...REFRIGERANT CIRCUIT DIAGRAM 21 QUIETCO2OL AIR COOLED MT Version LT Version ...
Страница 25: ...REFRIGERANT CIRCUIT DIAGRAM 22 QUIETCO2OL WATER COOLED VERSION MT Version LT Version ...
Страница 30: ...USER INTERFACE 27 Navigation To navigate inside the menu tree use the following buttons ...
Страница 36: ......
Страница 43: ...APPENDIX 1 REFRIGERANT AND OIL CHARGE AIR COOLED VERSION 39 ...
Страница 44: ...APPENDIX 1 REFRIGERANT AND OIL CHARGE AIR COOLED VERSION 40 ...