SET-UP
– MANAGEMENT
.
Version 1.02
p.
4
1234 V1 L TEXT
Alarm text MIDDLE on analogue input 1 is sent
when the value becomes higher than the value
defined in Point 1/yyyy or lower than the value in
Point 2/zzzz (
Vx M yyyy zzzz
).
1234 V1 B TEXT
Alarm text HIGH on analogue input 1 is sent when
the value becomes higher than the value defined in
Point 2/zzzz (
Vx M yyyy zzzz
).
Activate output in
case of alarm
1234 Gx
x = 1-9 (1 = 10 sec., 2 = 20 sec., 3 = 30 sec., 4 = 1
min, 5 = 2 min, 6 = 4 min, 7 = 8 min, 8 = 16 min
and 9 = constant.)
Sets the relay output to activate in x time in case of
alarm on an input.
Outputs follow
condition on inputs
1234 GA
Indicates that the output follows the corresponding
input if text is created.
Notice: input signal has higher priority than
command
S0
(S + zero) and
B0
(B + zero)
For further help: see the manual on the CD or on
Management of relay and functions with call from telephone
Relay:
Call the unit. Type in 1234 (password) when the connection is established, and await two ’beeps’. Type in
the chosen code and end the call.
Code examples:
*00 (as zero + zero)
Pulses relay output for 10 sec.
*10 (as 1 + zero)
Opens relay output
*20 (as 2 + zero)
Closes relay output
Macro:
Call the unit. When the connection is established, type in the chosen code and end the call.
x (x = 0-9 for macro 0-9)
Executes macro x