background image

4

ProFitter

TM

 Operating Instructions and Parts Manual

3VE59C

Figure 4 – Hose and Inlet Connector

Hose

Inlet Connector

Installation

Review and under-

stand all of the 

warnings in the Safety Information 

Section on pages 1–3. They are required to 

operate this heater safely. Follow all local 

and state codes when operating this 

heater.

After installing  

all gas piping, and 

making the proper connections, be sure 

to check for leaks. Apply a 50/50   

mix ture of dish soap and water to  

all connections. Bubbles forming are 

evidence of a leak. Be sure to correct  

all leaks at once!

1. Provide propane supply system as 

outlined above.

2. Connect POL fitting on hose/regulator 

assembly to propane tank(s) by turn ing 
the fitting COUNTER CLOCKWISE 

 

into the threads on the valve on top of 
the tank. Finish by tightening firmly, 
using 7/8” (22.2 mm) wrench.

IMPORTANT:

 To protect the regulator 

from weather damage, tighten the 
fitting with the black adjustment knob 
pointing down.

3. Connect female end of hose to the 

inlet connector of the heater, and 
tighten firmly with a wrench.

IMPORTANT:

 Use extra piping or hose 

if necessary to connect the heater to the 
gas supply, but always use the regulator
supplied with the heater.

4. Open supply valve on propane tank(s) 

SLOWLY.

NOTE:

 If this valve is not opened slowly, 

the excess flow check valve on the 
tank will interrupt the gas flow. If this 
happens, close the supply valve and 
reopen slowly.
5. Adjust the regulator to between 7 

and 10 PSIG.

Do not adjust the 

regulator above 10 

PSIG or below 7 PSIG, or the heater may 

not operate properly.
6. Check all connections for leaks.

Never use an open 

flame to check for 

leaks. Apply a 50/50 solution of liquid 

dish soap and water to check all 

connections. Correct all leaks 

immediately.
7. Close propane supply valv

e.

Ventilation

Always follow the 

minimum fresh air 

ventilation requirements. If these 

guidelines are not followed, carbon 

monoxide poisoning can occur. Always 

provide proper amounts of fresh air 

before operating this heater.

Provide at least three square feet (0.28 m²) 
of fresh, outside air for each 100,000 BTU/
Hr of rating. This heater requires  
a fresh air opening of at least 11.25 square 
feet (1.05 m²). Provide extra fresh air if 
more heaters are being used.

 

WARNING

Air Quality Hazard  

• Do not use this heater for heating 
human living quarters.
• Use of direct-fired heaters in the 
construction environment can result in 
exposure to levels of CO, CO2, and
NO2 considered to be hazardous to 
health and potentially life threatening.
• Do not use in unventilated areas
• Know the signs of CO and CO2 
poisoning
   - Headaches, stinging eyes
   - Dizziness, disorientation
   - Difficulty breathing, feels of being 
suffocated
• Proper ventilation air exchange (OSHA 
29 CFR 1926.57) to support combustion 
and maintain acceptable air quality 
shall be provided in accordance with 
OSHA 29 CFR Part 1926.154, ANSI 
A10.10 Safety
Requirements for Temporary and 
Portable Space Heating Devices and 
Equipment used in the Construction 
Industry or the Natural Gas and Propane 
Installation Codes CSA B149.1
• Periodically monitor levels of CO, CO2 
and NO2 existing at the construction 
site – at the minimum at the
start of the shift and after 4 hours.
• Provide ventilation air exchange, 
either natural or mechanical, as 
required to maintain acceptable indoor
air quality 

Figure 3 –  Regulator with Vent Pointing 

Down

POL Fitting

Supply 

Valve

Hose

Regulator

Propane/LP 

Tank

Adjustment Knob 

(Pointing Down)

NEVER LEAVE THE HEATER

UNATTENDED WHILE BURNING!

E

N
G

L

I

S

H

ProFitter

TM

Propane Construction Heater

For Technical Support or Troubleshooting, Call: 1-877-447-4768, 8:30 am - 4:30 pm CST         www.ghpgroupinc.com

Содержание RMC-FA300PF

Страница 1: ...OPERTY LOSS OR DAMAGE FROM THE HZARARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOXIDE POISONING AND OR ELECTRIC SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTION MANUAL LABELS ETCETERA CONTACT THE MANUFACTURER General Safety Information IMPORTANT Be sure to read and understan...

Страница 2: ...ces a small amount of carbon monoxide Humans can tolerate small amounts of carbon monoxide for short periods Carbon monoxide can build up in a heated space and failure to provide adequate ventilation could result in poisoning or death For either indoor or outdoor use Adequate ventilation shall be provided in accordance with OSHA 29 CFR 1926 154 Safety Requirements for Temporary and Portable Space ...

Страница 3: ... SAFETY CONTROL SYSTEM This system shuts the heater down if the flame is extinguished The fan and motor will continue to operate butthere will not be any heat PROPANE SUPPLY All propane gas and tanks are to be provided by the user This heater should only be used with a tank that has a vapor withdrawal system Refer to the Standard of Storage and Handling of Liquefied Petroleum Gas ANSI NFPA 58 Chap...

Страница 4: ...ns Correct all leaks immediately 7 Close propane supply valve Ventilation Always follow the minimum fresh air ventilation requirements If these guidelines are not followed carbon monoxide poisoning can occur Always provide proper amounts of fresh air before operating this heater Provide at least three square feet 0 28 m of fresh outside air for each 100 000 BTU Hr of rating This heater requires a ...

Страница 5: ... and Ontario Workplaces Reg 833 25 ppm 5000 ppm 3 ppm Reg 833 Canada STEL 15 minutes Reg 833 1 hour WSBC WorkSafe BC OHS Guidelines Part 5 1 and Ontario Workplaces Reg 833 100 ppm 15000 ppm WSBC 30000 ppm Reg 833 1 0 ppm WorkSafeBC 5 0 ppm Reg 833 Ensure that the flow of combustion and ventilation air exchange cannot become obstructed As the building tightens up during the construction phases vent...

Страница 6: ...eset and you can try to light the heater once again TO SHUT DOWN HEATER 1 Tightly close control valve on propane tank s 2 Give the heater a few seconds to burn the gas still left in the hose 3 Turn on off switch to the OFF position 4 Unplug extension cord from power source TO RESTART HEATER NOTE If the safety control stops the flow of gas to the heater the motor will continue to run To restart the...

Страница 7: ...ft replace fan as shown in Figure 7 Tighten setscrew firmly be careful not to overtighten 10 Reconnect lead wires as shown in the Wiring Diagram Figure 8 11 Reassemble base fan guard and base lower IGNITOR The only maintenance necessary for the ignitor is to be sure that the gap between the electrodes is kept between 10 and 15 2 5 3 8 mm The ignitor is accessible through the combustion chamber Sto...

Страница 8: ...ing Instructions and Parts Manual RMC FA300PF If any original wiring as supplied with the heater must be replaced it must be replaced with type AWG105 C wire or its equivalent except as indicated Type SF2 200 SGI 250 C Figure 8 Wiring Diagram NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING E N G L I S H ProFitterTM Propane Construction Heater For Technical Support or Troubleshooting Call 1 877 447...

Страница 9: ...Notes ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Technical Support or Troubleshooting Call 1 877 447 4768 8 30 am 4 30 pm CST www ghpgroupinc com ...

Страница 10: ...55 56 57 58 24 23 22 12 20 14 13 15 16 17 18 19 21 7 9 10 11 8 26 For Technical Support or Troubleshooting Call 1 877 447 4768 ProFitterTM Dyna GloTM Operating Instructions and Parts Manual 10 ProFitterTM Operating Instructions and Parts Manual RMC FA300PF NEVER LEAVE THE HEATER UNATTENDED WHILE BURNING For Repair Parts call 1 877 447 4768 Please provide following information Model number Serial n...

Страница 11: ...01633 1 34 Power Cord Assembly 2201163 1 35 Switch 2201549 1 36 Solenoid Valve 2315449 1 37 Screw 2001206 2 38 Connector Inlet 2315595 1 39 Fitting 2315596 1 40 Solenoid Valve Bracket 2315594 1 41 Screw 2000416 2 42 Nut 2000384 2 43 Back Pressure Switch 2201594 1 44 Base Lower 2315589 1 45 Screw 2001355 6 46 PCB Assembly 2201181 1 47 Screw 2001445 2 48 Nut 2000231 2 49 Base 2315588 1 50 Plastic Tu...

Страница 12: ...r cord and extension cord for cuts and breaks 2 Be sure that housing is not damaged Make sure there are no obstructions to the fan 3 Straighten blade s to match others 4 Replace motor 1 Check igniter wire Reattach or tighten if loose Check spark module Replace if necessary Check all electrical components 2 Set gap to 0 08 2 mm 3 Replace spark plug 1 If the heaters output is restricted internal tem...

Страница 13: ...how long an implied warranty lasts so the above limitation may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you CLAIMS HANDLED AS FOLLOWS 1 Contact your retailer and explain the problem 2 If the retailer is unable to resolve the problem contact ourCustomer Service Dept detailing th...

Страница 14: ...s SAVE THIS CARD Place Postage Stamp Here GHP Group Inc 8280 Austin Avenue Morton Grove IL 60053 3207 GHP Group Inc 8280 Austin Ave Morton Grove IL 60053 3207 Tel 877 447 4768 www ghpgroupinc com 8280 Austin Avenue Morton Grove IL 6 0 0 5 3 3 2 0 7 Tel 847 324 5900 Fax 847 324 5901 Toll Free 877 GHP Group 8 7 7 4 4 7 4 7 6 8 www ghpgroupinc com GHP GHP Group Inc 6440 W Howard St Niles IL 60714 330...

Отзывы: