USER GUIDE

PEL 1000 / PEL 1000-M

8 (8) 

 

Produal Oy 

Keltakalliontie 18, 48770 Kotka FINLAND 

Tel: +358 10 219 9100 / Fax: +358 5 230 9210 

[email protected] 

www.produal.com 

Information is subject to change without prior notice. 

Input registers (read only) 

Register 

Parameter description 

Data type 

Value 

Range 

3000

Pressure measurement 

signed 

0…1100 

0…1100 Pa 

3000

Selected pressure range 

unsigned 

0 - 1 

0 =  0…500 Pa 
1 =  0…1000 Pa /  

custom *) 

3000

Zero value of the sensor 

signed 

-200…200 

-200…200 Pa 

3000

Analogue output voltage 

unsigned 

0…1000 

0…10.00 V 

*) 

The custom range is 0…1000 Pa as a default. The range can be changed by using ML-SER tool or by defining the high limit to the 
Modbus register 40006 (the low limit is 0 Pa). 

Holding registers (read / write) 

Register 

Parameter description 

Data type 

Value 

Range 

Default 

4000

Control mode 

unsigned 

0 - 1 - 2 

0 =  off 
1 =  P 
2 =  PI 

4000

Set point 

unsigned 

0…1000 

0…1000 Pa 

 

4000

Proportional band 

signed 

5…1000 

0.5…100 % 

500 

4000

Integration time 

signed 

2…5000 

2…5000 s 

10 

4000

Output mode 

unsigned 

0 - 1 

0 =  0…10 V 
1 =  2…10 V 

4000

Custom range high limit (low limit = 0 Pa) 

unsigned 

1…10 

100…1000 Pa 

10 

 

Содержание Sensortec PEL 1000-M

Страница 1: ...n open surrounding space pressure Accordingly the duct under pressure is detected by connecting the measuring point to connector and by leaving the connection open Install the measuring hoses carefull...

Страница 2: ...cond when the power is connected The indicator light illuminates when the transmitter sends data to Modbus M models only Selecting measuring range Measuring range can be selected with the jumper S1 A...

Страница 3: ...e after one hour of powering the transmitter 1 Unplug the plastic tubes from the inlets 2 Press the zeroing button until the indicator light lights up without flashing A Indicator light B Zeroing butt...

Страница 4: ...ER tool You can proceed in the menu by pressing the M and OK buttons The values can be changed with the and buttons The value is accepted with the OK button The following menu structure contains the f...

Страница 5: ...source calibration pressure must be at least 275 Pa Hoses for pressure connections Calibration 1 Connect the transmitter and the reference pressure meter to the same pressure source 2 Connect the ML S...

Страница 6: ...lected pressure range Custom range menu The CUSTOM RANGE menu is for setting the custom pressure range limits The custom range is in use when all the pressure range selection jumpers are placed Output...

Страница 7: ...Modbus can be terminated by placing the Modbus termination jumper S7 A Modbus termination jumper Supported Modbus functions 0x01 Read Coils 0x02 Read Discrete Inputs 0x03 Read Holding Registers 0x04 R...

Страница 8: ...200 200 200 200 Pa 30004 Analogue output voltage unsigned 0 1000 0 10 00 V The custom range is 0 1000 Pa as a default The range can be changed by using ML SER tool or by defining the high limit to the...

Отзывы: