Input registers (read only)
Register
Parameter description
Data type
Value
Range
3000
1
Pressure measurement
signed
0…1100
0…1100 Pa
3000
2
Selected pressure range
unsigned
0 - 1
0 = 0…500 Pa
1 = 0…1000 Pa /
custom *)
3000
3
Zero value of the sensor
signed
-200…200
-200…200 Pa
3000
4
Analogue output voltage
unsigned
0…1000
0…10.00 V
*)
The custom range is 0…1000 Pa as a default. The range can be changed by using ML-SER tool or by defining the high limit to the
Modbus register 40006 (the low limit is 0 Pa).
Holding registers (read / write)
Register
Parameter description
Data type
Value
Range
Default
4000
1
Control mode
unsigned
0 - 1 - 2
0 = off
1 = P
2 = PI
0
4000
2
Set point
unsigned
0…1000
0…1000 Pa
4000
3
Proportional band
signed
5…1000
0.5…100 %
500
4000
4
Integration time
signed
2…5000
2…5000 s
10
4000
5
Output mode
unsigned
0 - 1
0 = 0…10 V
1 = 2…10 V
0
4000
6
Custom range high limit (low limit = 0 Pa)
unsigned
1…10
100…1000 Pa
10