USER GUIDE
PEL 1000 / PEL 1000-M
7 (8)
Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
Tel: +358 10 219 9100 / Fax: +358 5 230 9210
www.produal.com
Information is subject to change without prior notice.
MODBUS
Bus properties
Protocol
RS-485 Modbus RTU
Bus speed
9600/19200/38400/57600 bit/s
Data bits
8
Parity none/odd/even
Stop bits
1
Network size
up to 127 devices per segment
Bus termination
The Modbus can be terminated by placing the Modbus termination jumper (S7).
A. Modbus termination jumper
Supported Modbus functions
0x01 Read
Coils
0x02
Read Discrete Inputs
0x03
Read Holding Registers
0x04
Read Input Registers
0x05
Write Single Coil
0x06
Write Single Register
0x0F
Write Multiple Coils
0x10
Write Multiple Registers
0x17
Read/Write Multiple Registers
Modbus registers
Data types:
bit
=
0 or 1
unsigned =
unsigned
integer
(0…65535)
signed =
integer
(-32768…32767)
Discrete inputs (read only)
Register
Parameter description
Data type
Value
Range
1000
1
Zeroing button is pressed within 1 minute
bit
0…1
no=0, yes=1