Communications menu (M models only) 

 

The Modbus settings can be changed through the COMMUNICATIONS menu. 

Calibration menu 

 

The CALIBRATION menu is for pressure measurement span calibration. To calibrate, you need to know the pressure 
measurement deviation at a single pressure. 

You need the following equipment for the calibration. 

- ML-SER 

tool. 

A reference pressure meter. 

A stable pressure source (calibration pressure must be at least 275 Pa). 

Hoses for pressure connections. 

Calibration 

1. 

Connect the transmitter and the reference pressure meter to the same pressure source. 

2. 

Connect the ML-SER to the transmitter. 

3. 

Navigate to the calibration menu. 

4. 

Read the pressure values from the ML-SER tool and the reference pressure meter. 

5. 

Press + and – buttons on the ML-SER tool to adjust the transmitter pressure measurement to same value as 
the reference. 

The measurement can be tuned ±25 Pa. 

+

Ac

tu

al

Measured

Pa

Pa

 

For example if you 5 Pa at 1000 Pa, the device will now read 1005 Pa at that pressure. 
Correspondingly reading is cor10 Pa at 2000 Pa. 

6. 

Press OK to save the span calibration. 

The calibration parameter values are displayed for two seconds before returning to the menu. 

Содержание Sensortec PEL 1000-M

Страница 1: ...n open surrounding space pressure Accordingly the duct under pressure is detected by connecting the measuring point to connector and by leaving the connection open Install the measuring hoses carefull...

Страница 2: ...cond when the power is connected The indicator light illuminates when the transmitter sends data to Modbus M models only Selecting measuring range Measuring range can be selected with the jumper S1 A...

Страница 3: ...e after one hour of powering the transmitter 1 Unplug the plastic tubes from the inlets 2 Press the zeroing button until the indicator light lights up without flashing A Indicator light B Zeroing butt...

Страница 4: ...ER tool You can proceed in the menu by pressing the M and OK buttons The values can be changed with the and buttons The value is accepted with the OK button The following menu structure contains the f...

Страница 5: ...source calibration pressure must be at least 275 Pa Hoses for pressure connections Calibration 1 Connect the transmitter and the reference pressure meter to the same pressure source 2 Connect the ML S...

Страница 6: ...lected pressure range Custom range menu The CUSTOM RANGE menu is for setting the custom pressure range limits The custom range is in use when all the pressure range selection jumpers are placed Output...

Страница 7: ...Modbus can be terminated by placing the Modbus termination jumper S7 A Modbus termination jumper Supported Modbus functions 0x01 Read Coils 0x02 Read Discrete Inputs 0x03 Read Holding Registers 0x04 R...

Страница 8: ...200 200 200 200 Pa 30004 Analogue output voltage unsigned 0 1000 0 10 00 V The custom range is 0 1000 Pa as a default The range can be changed by using ML SER tool or by defining the high limit to the...

Отзывы: