BACnet Standard Object
Types Supported
No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed
functions within the proprietary control application of the product as follows
410
Current Hour
Unsigned 16
0..23
0..23
411
Current Minute
Unsigned 16
0..59
0..59
412
Current Day
Unsigned 16
1..31
1..31
413
Current Month
Unsigned 16
1..12
1..12
414
Current Year
Unsigned 16
2015..2099
2015..2099
415
Current Hour Update Register
Unsigned 16
0..23
0..23
416
Current Minute Update Register
Unsigned 16
0..59
0..59
417
Current Day Update Register
Unsigned 16
1..31
1..31
418
Current Month Update Register
Unsigned 16
1..12
1..12
419
Current Year Update Register
Unsigned 16
2015..2099
2015..2099
420
Update Time
Unsigned 16
0..1
0 = No Action
1 = Update
Register
Parameter Description
Data Type
Raw Data
Range
Object
Number Of
Instances
Instance Assignments
Device Object
1
Analogue Value
Please note AV1 - AV10 are Read Only
31
AV(0) –Built-In Sensor (Read/Only
2
)
AV(1) - RI_1 (RI1 Temperature / AI1, R/O
2
)
AV(2) - RI_2 (RI2 Temperature / AI2,R/O
2
)
AV(3) - Target (Calculated Setpoint, (R/O
2
)
AV(4) - Humidity (Read/Only
2
)
AV(5) - CO2 (Read/Only
2
)
AV(6) - Fan Demand (R/O
2
)
AV(7) - Thermic1 Demand
AV(8) - Thermic2 Demand
AV(9) - Nominal Setpoint (Read/Only
2
)
AV(10) – Heating DZ Comfort
AV(11) – Cooling DZ Comfort
AV(12) – Heating DZ ECO
AV(13) – Cooling DZ ECO
AV(14) – Frost SP
AV(15) – Y1 Minimum
AV(16) – Y1 Maximum
AV(17) – Y2 Minimum
AV(18) – Y2 Maximum
AV(19) – Y3 Minimum
AV(20) – Y3 Maximum
AV(21) - PB (Proportional Band)
AV(22) – IA (Integral Action)
AV(23) – Brightness (LCD)
AV(24) - Network Temp.
AV(25) – CO2 SP (CO2 Setpoint)
AV(26) – Humidity SP (Humidity Setpoint)
AV(27) – Y1 Output
3
AV(28) – Y2 Output
3
AV(29) – Y3 Output
3
AV(30) - Aux. SP (Auxiliary Loop Setpoint)
Binary Value
Please note BV0, BV1 are Read Only
9
BV(0) – DI_1 (Digital Input 1) (Read/Only
2
)
BV(1) – Boost Status (Read/Only
2
)
BV(2) - OFF Status
1
BV(3) - ECO Status
1
BV(4) – Lock
1
BV(5) – Change-Over
BV(6) - Update Nonvol
BV(7) - DO_1 (Digital Output 1)
BV(8) - DO_2 (Digital Output 2)
MutliState Value
3
MSV(0) - Device Mode (1=Comfort,
2=ECO, 3=OFF, 4 = Boost)
MSV(1) - Alarm (Binary Coded -
Add 1 to
to bit values)
MSV(2) - Fan Speed Override (1 = Auto, 2
= Man_0, 3=Man_1, 4=Man_2, 5=Man_3,
6=Man_4, 7=Man_5, 8=Man_6)