Produal Oy
Copyright © 2020 Produal Oy - All rights reserved - 07/2020
PS
6001TRC-P
- 21/34
Web-site:
www.produal.com
Enquiries: T:
+358 10 219 9100
E:
Mode Button
COMFORT / ECO / OFF / BOOST Button Mode
Operation Mode
0 = Active (Default)
1 = Indication Only
FAN, BOOST, TIMES
Parameter Name
Description
Range
ALARMS
Parameter Name
Description
Range
Alarm 1 Source
Source for the Alarm Display
0 = CO2 Sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
Alarm 1 Amber Threshold
Alarm 1 Amber Backlight Switching Point
0..5000 (Default 0)
Alarm 1 Red Threshold
Alarm 1 Amber Backlight Switching Point
0..5000 (Default 0)
Alarm 1 Hysteresis
Hysteresis for Alarm 1
0..5000 (Default 0)
Alarm 2 Source
Source for the Alarm Display
0 = CO2 Sensor
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
Alarm 2 Amber Threshold
Alarm 2 Amber Backlight Switching Point
0..5000 (Default 0)
Alarm 2 Red Threshold
Alarm 2 Amber Backlight Switching Point
0..5000 (Default 0)
Alarm 2 Hysteresis
Hysteresis for Alarm 2
0..5000 (Default 0)
SYSTEM
Parameter Name
Description
Range
Address
Modbus Address (Only Modbus versions)
BACnet MAC Address (Only BACnet versions)
0..247 (Default 1)
0..127 (Default 1)
Baud Rate (Only Modbus/BACnet versions)
Modbus / BACnet Baud Rate
0 = 9600 (Default)
1 = 19200
2 = 38400
3 = 57600
4 = 76800
Parity (Only Modbus/BACnet versions)
Parity
0 = None (Default)
1 = Odd
2 = Even
Stop Bits (Only Modbus/BACnet versions)
Stop Bits
0 = 1 Stop Bit (Default)
1 = 2 Stop Bits
Device ID (Only BACnet versions)
BACnet Device ID
0..4,194,303
(Default Auto=651001)
Service Pin (Only BACnet versions)
Bacnet Service Pin (when activated the device
sends BACnet I-AM message)
0 = Disabled (default)
1 = Enabled
Brightness
Backlight Brightness
0..20 (default 5)
Show Unit Swap
Shows the Fahrenheit / Celcius Unit Selection
Button
0 = Disabled (default)
1 = Enabled
Lock Mode
Lock Operation
0 = Disabled (default)
1 = On /Off Only (Lights & Blinds)
2 = Temp Adjust Only Available
3 = No Input - All Buttons Disabled
Lock Code
Lock Mode Password
0000 - 9999 (default 0000)
Maintenance Code
Maintenance Mode Password
0000 - 9999 (default 6666)
Staff Code
Staff Page Password - Access Password to Further
Settings Screen
0000 - 9999 (default 0000 =
disabled)
Language
Language
EN = English (Default)
FR = French
Native Units (Defaults)
Selects either Fahrenheit / Celsius as Native Units
NOTE: RELOADS DEFAULTS
C = Celsius (default)
F = Fahrenheit
Auto Daylight Savings
Automatic Summer/Winter Time Adjustment
0 = Disabled (default)
1 = Enabled
Screen Cycle Speed
Cycle Speed of Measurements in the ACTION RING
Fast = 4.3 secs, Medium = 7.8 secs, Slow = 10.8
secs
0 = Fast
1 = Medium (default)
2 = Slow
Screen Refresh Rate
Refresh Rate of the LCD Screen
0 = Fast (default)
1 = Medium
2 = Slow