If Sensor >=Amber Threshold; Alarm = Amber

If Sensor >= Red Threshold; Alarm = Red

Hysteresis acts to prevent a return to a lower alarm level until the Sensor value falls to a Threshold - 
Hysteresis

LOW LIMIT ALARM

If the Amber threshold is set higher than the Red Threshold then:

If Sensor <= Amber Threshold; = Amber

If Sensor <= Red Threshold; Alarm = Red

Hysteresis acts to prevent a return to a lower alarm level until the Sensor value rises to a Thr 
Hysteresis.

Sensor Fault Display

When entering FURTHER 
INFORMATION AND SETTINGS 
screen and a sensor/input fault is 
active, select the fault icon for more 
information. 

FURTHER SETTINGS AND 
INFORMATION

SELECT FAULT ICON FOR MORE 
INFORMATION

Notifications

Internal Sensor Failure
Remote  Sensor 1 Fault

Digital Contact Fault

Remote  Sensor 2 Fault

The typical alarm reasons are:

External sensor 1 (Res1) fault 
(when activated; out of range)

External sensor 2 (Res1) fault 
(when activated; out of range)

Built-in sensor fault

Digital Input Alarm

Controller Status 
Information Display

After entering CONFIGURATION 
PARAMETER GROUP screen and 
selecting the INFO icon it is possible 
to see the current status information 
of the controller. The page shows the 
current measurement and output 
information.

LIVE INFORMATION
SCREEN

SELECT INFO ICON FOR 

Status Information

Built-In Sensor

24.8 

RI_1

12.8

RI_2

--.- 

DI_1

On

CO2 1200 
Humidity 51.7
Target

21.7 

Heating Demand 

78

Cooling Demand 

0

Fan Demand 

78

CO2 Demand 

65

Humidity Demand 

12 

AO1 78 
AO2 65 
AO3 12 

De-Hum Demand 

Operating Modes

Parameter Groups

Display

Control Settings

Measurements

Network

Configuration Parameters

Nominal Setpoint

21.0

Control Settings

Fan, Boost, Lights & Blinds

Parameter Groups

Alarms

Control Settings

Inputs & Outputs

System

Heating DZ COMFROT

0.5

Cooling DZ COMFORT

0.5

Heating DZ ECO

4.0

ENTER MAINTENANCE CODE FOR 
MAINTENANCE MODE 

CLICK TO ACCESS SETTINGS 
GROUP

CLICK TO CHANGE 
SETTING

ACCESS 
MORE 
SETTINGS

6666

8 9
5 6 -
2 3

Esc

OK

Del

Maintenance Code

Enter Code

7
4
1
0

The TRC-P devices are configured to operate in different modes via the configuration parameters 
accessible through the maintenance mode.

To enter the maintenance mode click the COG WHEEL icon in the FURTHER SETTINGS SCREEN 
and enter the maintenance mode password (default 6666).

Содержание 6001TRC-P

Страница 1: ...sh Mounting in the US UK or EURO Wall Mounting Box Built In Temperature Sensor up to 2 x Remote NTC10 Sensors Wide Range of Input and Output Configurations Digital Input for Overrides Control of up to...

Страница 2: ...nge 0 5000ppm CO2 Accuracy 50ppm 3 of the reading 25 C 77 F Technology Auto Calibrating Patented Non Dispersive Infrared NDIR Non Linearity 1 FS Warm Up Time 20 seconds Response Time 2 minutes Humidit...

Страница 3: ...4 5mm Weight 220g CONN DESCRIPTION Y1 0 10Vdc Analogue Output 1 default fan speed Y2 0 10Vdc Analogue Output 2 default heating stage 1 Y3 0 10Vdc Analogue Output 3 default cooling stage 1 24V 24Vac dc...

Страница 4: ...RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS...

Страница 5: ...On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac 1A Triac...

Страница 6: ...s based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz Deadzone ENERG...

Страница 7: ...mmed to the stand by level Pressing the DIM icon when the device is in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings...

Страница 8: ...emand is 0 With PI control if the temperature remains in the deadzone for a prolonged period the heating cooling demand ramps to 0 The deadzone allows the temperature to fluctuate around the setpoint...

Страница 9: ...e formula Setpoint_Reset Limit_Setpoint Temperature Limit_Ratio NOTE The target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effec...

Страница 10: ...A 2 A 3 R 1 A 2 T 0 1 0 V d c T R C P 1 A 2 T P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching...

Страница 11: ...oint regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period in order t...

Страница 12: ...ATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY CONT...

Страница 13: ...Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0 100 Cleaning Mode After entering FURTHER INFORMATION screen by selecting the CLEANING ico...

Страница 14: ...re not instantaneous Therefore they are not suitable for fast switching transition will be missed during the inherent delay time Note RI2 is not available with TRC P 2A3R 2 x 0 10Vdc Input AI Options...

Страница 15: ...ge percentage The connected control loop output 0 100 is then scaled from minimum voltage to maximum voltage For example in the EC fan control if the fan is required to run always at minimum level the...

Страница 16: ...e mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Analogue Output Scaling Anti JAM is not available in the 6 Port and 6 Port Reverse modes Number of Heating and...

Страница 17: ...ault Digital Input Alarm Controller Status Information Display After entering CONFIGURATION PARAMETER GROUP screen and selecting the INFO icon it is possible to see the current status information of t...

Страница 18: ...t 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Direction 0 Reverse Default 1 Direct Heating Stage 2 Dir Heating Stage 2 Direction 0 Reverse Default 1 Direct Cooling Stages Number of Cooling Stages 0...

Страница 19: ...sabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Digital Inpu...

Страница 20: ...Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period TRC P 1A2T TRC H 3R2T 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Страница 21: ...0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Default 1 2 Stop Bits...

Страница 22: ...eter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode Override 0...

Страница 23: ...Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Unsigned 16 0 2 0...

Страница 24: ...verride Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Default 0 0 1...

Страница 25: ...16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16 0 480 0...

Страница 26: ...00 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns to 0 The blinds...

Страница 27: ...2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching Time 3 Targ...

Страница 28: ...2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16 0 2400 0...

Страница 29: ...alogue Value Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humid...

Страница 30: ...ies 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2 2 Stages...

Страница 31: ...ng Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Network NTC10...

Страница 32: ...igned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone 1 5 Zone...

Страница 33: ...s Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192 Aux Lo...

Страница 34: ...ual com Enquiries T 358 10 219 9100 E info produal fi NOTE Information is subject to change without prior notice Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112...