Procom EL250TYLA-B Скачать руководство пользователя страница 5

5

4

       

WARNING:   Rework   worksheet,  adding   the  space  of   the  adjoining  unconfined  space.  The

combined  spaces  must   have  enough  fresh air  to supply  all  appliances  in  both  spaces.

If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.

3. Add  the  Btu/Hr of all fuel burning appliances in the space.

     Vent-free heater                                                       Btu/Hr
     Gas water heater*                                                   Btu/Hr
     Gas furnace                                                              Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                        Btu/Hr
     Total                                =                                         Btu/Hr

    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.

4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.

                         

Btu/Hr (maximum the space can support)

                          

Btu/Hr (actual amount of Btu/Hr used)

         

Example

 :  51,200 Btu/Hr(maximum the space can support)

                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. 

See  Ventilation  Air  From

Inside  Building

 (below).

B.  Vent  room  directly  to  the  outdoors. See  

Ventilation  Air  From  Outdoors

 (below) .

C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.

Figure  2 -Ventilation  Air  from  Inside  Building

 Example:
 Gas  water  heater          30,000        Btu/Hr
  Vent-free  heater    +       26,000        Btu/Hr
  Total                          =      56,000        Btu/Hr

This  fresh air  would come  from an adjoining  uncon-
fined space.  When  ventilating  to  an  adjoining
unconfined space, you  must  provide  two  perma-
nent  openings: one within 12" of  the  ceiling  and
one  within 12" of  the  floor on  the  wall  connecting
the  two  spaces (see  options 1 and  2, Figure 2).
You  can  also  remove  door  into adjoining  room
(see  option 3, Figure 2). Follow  the  National  Fuel
Gas  Code. NFPA  54/ANSI  Z223.1.  Section 5.3,
Air  for  Combustion  and  Ventilation  for required
size of  ventilation grills or ducts.

Ventilation  Air  From  lnside  Building

Ventilation  Air  From Outdoors

Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12" of the
floor. Connect these items directly to the outdoors or
spaces open to the outdoors. These spaces include
attics and crawl spaces. Follow the National Fuel
Gas Code, NFPA 54/ANSI Z223.1, Section 5.3. Air
for Combustion and Ventilation for required size of
ventilation grills or ducts.

IMPORTANT:Do not provide openings for  inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the
attic will activate the power vent.

Figure  3 -Ventilation  Air  from  Outdoors

WARNING: 

If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the
methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation, or
applicable local codes.

Содержание EL250TYLA-B

Страница 1: ...f sale not for pur pose of resale from the manufacturer Safety Information Warnings 2 Air for Combustion and Ventilation 4 Installation 6 Operating heater 9 Cleaning Maintenance 10 Trouble Shooting 11...

Страница 2: ...d in a bedroom or bathroom erating heater 5 Do not use this heater as a wood burning heater Use only the logs pro vided with the heater 6 Do not add extra logs or ornaments such as pine cones vermicul...

Страница 3: ...ct of gas combustion An unvented room heater productes approximately one 1 ounce 30ml of water for every 1 000 BTU s 3KW s of gas input per hour Unvented room heaters are recommended as supplemental h...

Страница 4: ...ining if You Have a Confined or Unconfined Space Use this worksheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining...

Страница 5: ...Figure 2 Ventilation Air from Inside Building Example Gas water heater 30 000 Btu Hr Vent free heater 26 000 Btu Hr Total 56 000 Btu Hr This fresh air would come from an adjoining uncon fined space Wh...

Страница 6: ...vinyl or cloth wall coverings or operating heater where impurities such as tobacco smoke aromatic candles cleaning fluids oil or kerosene lamps etc in the air exist may dis color walls IMPORTANT Vent...

Страница 7: ...1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Installation must include an equip ment shutoff valve union and plugged 1 8 NPT tap...

Страница 8: ...xture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for lea...

Страница 9: ...sition 4 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information on page 2 If you don t smell gas go to the next s...

Страница 10: ...e To Turn Off Gas to Appliance page 9 see Troubleshooting pages 11 through 12 CLEANING AND MAINTENANCE WARNING Turn off heater and let cool before cleaning CAUTION You must keep c o n t r o l a r ea s...

Страница 11: ...may become blocked by debris or rust with no flame present If so turn off heater and let cool Either remove blockage or replace burner Blocked burner flame holes will create soot TROUBLE SHOOTING Not...

Страница 12: ...1 C l e a n b u r n e r s e e C l e a n i n g and Maintenance page 10 or replace burner orifice 2 Contact local propane LP gas company 3 Replace burner orifice 4 Reconnect leads Delayed ignition burne...

Страница 13: ...mensions Inches H W D Stove 38 3 16 26 3 8 14 1 8 Carton 37 29 5 16 15 5 16 41 3 8 x29 5 16 x17 3 8 Weight lbs Stove 73 78 73 78 Shipping 89 94 89 94 For purposes of input adjustment The carton dimens...

Страница 14: ...e will ask you to return the defective part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product Call PRO COM at 877 886 5989 for referral information When calling PRO CO...

Страница 15: ...1 5 14 ILLUSTRATED PARTS BREAKDOWN EL250TYLA B EL250TYLA W EL250TYLB O EL250TYLA C EL250TYLB DO EN250TYLA B EN250TYLA W EN250TYLB O EN250TYLA C EN250TYLB DO...

Страница 16: ...e parts used in your heater When ordering parts follow the instructions listed under Replacement Parts on page 14 of this manual EL250TYLA B EL250TYLA W EL250TYLB O EL250TYLA C EL250TYLB DO EN250TYLA...

Страница 17: ...1 7 16 ILLUSTRATED PARTS BREAKDOWN EL250TYLA B EL250TYLA W EN250TYLA B EN250TYLA W...

Страница 18: ...1 8 12 17 PARTS LIST EL250TYLA B EL250TYLA W EN250TYLA B EN250TYLA W...

Страница 19: ...1 9 18 ILLUSTRATED PARTS BREAKDOWN EL250TYLB O EN250TYLB O EN250TYLB C EL250TYLB C EN250TYLB DO EL250TYLB DO...

Страница 20: ...2 0 19 PARTS LIST EL250TYLB O EN250TYLB O EN250TYLB C EL250TYLB C EN250TYLB DO EL250TYLB DO...

Страница 21: ...g logs Fasten decorating logs 1 2 3 onto the correspondent angle iron Figure 4 Insert the pinhole on the upper part of log 4 into the pin on the left side of log 1 Place the lower part on the flat roo...

Страница 22: ...ear panel and place it on the mounting bracket in the door Mounting operating control housing to the mounting bracket with two screw see figure 4 B EN L 250TYLBmodel Insert opera tion control housing...

Страница 23: ...Power Cord WiringDiagram Decal INSTALLING BLOWER ACCESSORY BLOWER ACCESSORY MODEL NFHTX186 Figure 3 A Routing Power Cord Figure 5 Mounting Control Housing MODEL EL N 250TYLB Figure 4 Mounting Control...

Отзывы: