Generator is stopped by releasing fuel
solenoid.
Generator contactor is released and mains
contactor is closed. Hooter shall be
activated
7
Generator
Supervision Time
The time for which the Generator voltage
should, continuously be unhealthy to
generate a fault condition.
10Sec
0-999
Sec.
8
Generator O/S
If the generator frequency goes beyond this
limit, genset shuts down immediately
65 Hz
40-80
Hz;
Disable
9
No. of Crank
Attempt
The maximum number of Cranks that shall
be issued to start the Generator
3
1-10
10
Crank Time
Maximum Crank time
10Sec
0-25Sec
11
Crank Delay
The delay between two successive Cranks
5
1-100Sec
12
Gen. pickup
Voltage
This is the ignition voltage of the genset
100V
80-150V
13
Generator warm up
time
After switching on the genset the load is
put on the genset on elapse of generator
warm up time
10 Sec
0-999
Sec.
14
Mains Restoration
Time
The time for which mains should be
continuously healthy before stopping the
Generator.
30Sec
0-999Sec
15
Generator
Recooling Time
The time for which Generator is allowed to
run on no load before switching off
30 sec
0-999Sec
16
Stop solenoid time
The time for which stop solenoid will be
kept active while stopping the engine
30Sec
0-100Sec
17
Low Fuel time
delay
Time delay before this fault can be
activated.
Faults are described in details.
5 Sec
0-999Sec
18
LLOP Time delay
Time delay before this fault can be
activated.
Faults are described in details.
5 Sec
0-999Sec
19
HWT Time delay
Time delay before this fault can be
activated.
Faults are described in details.
5 Sec
0-999Sec
20
GCB to MCB time
delay
Changeover time delay from generator to
mains
2Sec
1 –5 Sec
21
Hooter Reset Time
Time for which the hooter is switched on
after fault
30 Sec
0-999
Sec.
22
Over Current
If the Current increase beyond this setting
the genset shuts down after the O/C delay
(Available only in DGC-6 with single
phase mains monitoring)
25
1 –70
Amp
23
O/C Delay
Time for which the current has to be above
overcurrent setting before initiating shut
down process
(Available only in DGC-6 with single
10
0-999
Sec.
Cat/DCG-6D1I/07-08/03/Ver 1 Page 7/10