• Use the
↑
,
↓
,
←
,
→
keys to end the mea-
suring process of the
1st layer:
Fig. 5.10 Instructions
4 Smallest measured
cover of the 1st layer
• Place the cursor bet-
ween 2 rebars that are
as far apart as possible.
• Mark the position on
the measuring area.
• Start measuring the
bars in the 2nd layer
from this position.
• After the measuring
area has been scan-
ned, the following
display appears:
Fig. 5.11 Rebars of 2nd
layer
• Use the
↑
,
↓
,
←
,
→
keys to end the mea-
suring process of the
2nd layer. The smallest
concrete cover is indi-
cated.
• Press the PRINT/
STORE key to store
the measuring display.
• Press the END key if
the result must be
deleted.
16
Measuring Process
© 2007 Proceq SA
Measuring procedure
• Start with the END key.
The following display
appears:
Fig. 5.8
Scanning
display
• Determine the direction
of travel using the
↓
,
→
keys.
• Position the travel path
where the concrete ele-
ment is to be examined.
• Please note that loca-
ting and measuring is
in relation to the center
of the probe.
• After the measuring
area has been scan-
ned, the following is
displayed:
Fig. 5.9
Rebars of 1st
layer
• Travelling backwards
with the probe deletes
the displayed rebars.
1 Speed display. The
flow bar must be within
the scale.
2 Current concrete cover
3 Symbol for travelling
and scanning
The layer measured first
is displayed in thicker
lines.
1 2 3
4