From the FG terminal at the rear side of GLC unit, please take grounding exclusively

[within ground resistance of 100 

].

9

Precaution for Grounding

Please pay special attention to the following instructions when connecting the power
cable to the GLC unit.

If the supply voltage exceeds the GLC unit range, connect a voltage transformer.

For between the line and ground, select a power supply that is low in noise.  If there is an
excess amount of noise, connect a noise reducing transformer.

When supplying power to the GLC unit, please separate the input/output and operation
unit lines.

To increase the noise quality, simply twist the power cable before connecting it to the
GLC unit.

The power supply cable must not be bundled or kept close to main circuit lines (high
voltage, high current), or input/output signal lines.

Connect a surge absorber to deal with power surges.

To reduce noise, make the power cable as short as possible.

8

Precautions for Supplying Power

11

Replacing the Backlight

10

Precautions for Input/Output Signal Lines

Input and Output signal lines must be separated from the power control cables for op-
erational circuits.

if this is not possible, use a shielded cable and the shield should be grounded.

The backlight on this unit can be replaced.
For an explanation of how to replace it, please refer to the GLC300 Series User’s
Manual (sold separately) or the instruction manual which comes with replacement
backlights (sold separately).

Applicable backlight models

Using any backlight other than the applicable models shown above may cause
an accident or breakdown.

GP unit

Backlight model

GLC300-TC41-24V

GP577RT-BL00-MS

  If this is not possible, use a shielded, grounded cable.

Содержание GLC300-TC41-24V

Страница 1: ...e GLC If the GLC s internal program enters RUN mode prior to the I O unit s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Design a user program that will ensure the safety of the user s system in the event of a GLC display or control error or in the event of either a data transmission error or power failure between the GLC and a connected ...

Страница 2: ...e damaged if it falls off the back of the GLC or a system related malfunction or accident may occur due to I O data signal problems Be sure any data cable attached to the GLC s connector is securely attached If the cable and connector pins do not all make complete contact incorrect input or output signals can result General Wiring Cautions To prevent shocks or malfunctions GLC s FG earth wire shou...

Страница 3: ...rements Installation and operation instructions are provided with each GLC These installa tion instructions contain the following statements 1 Power input and output I O wiring must all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as specified in Section 18 152 of the Canadian Electrical Code for units installed within Canada an...

Страница 4: ...ontact your local GLC dis tributor immediately Package Contents User s Manual Sold Separately GLC300 User s Manual GLC Option Items Logic Program Development soft ware Sold Separately Pro Control Editor GLC Unit GLC300 TC41 24V Operation Instructions 1 this sheet Installation fasteners 4 pcs Operation Instructions Digital GLC300 MM01 ENG Digital GLC300 GLC300 GLC300 GLC300 GLC300 User s User s Use...

Страница 5: ...PLC C Power Lamp Lights up when the power is turned On Normally Green LED D Power Input Terminal Block The input and ground terminals for AC power cable E Auxiliary Input Output AUX Operates the Touch Switch System Alarm Buzzer Run outputs and Remote Reset inputs F Serial Interface RS 232C RS 422 Serial interface Connect to the Host G Printer Interface Connect the printer here H Tool Connector Con...

Страница 6: ...XM2A 2501 madebyOMRONCorp RecommendedCover Dsub25pinCover XM2S 2511 madebyOMRONCorp JackScrew XM2Z 0071 madebyOMRONCorp Use rough metric type M2 6 x 0 45p threads used to hold the cable s set fastening screws in place RecommendedCable CO MA VV SB5Px28AWG madebyHITACHICableLtd 1 13 14 25 Pin 14 can be used for the power supply for the user s optional equipment connected to the GLC Pin 14isnotprotec...

Страница 7: ...wareAlarm SCREENMEMORYCHECKSUMERROR Software Alarm SYSTEM ERROR i e incorrect data that makes continuation of screen operation impossible or when Watchdag Timer s Alarm output occurs11 RecommendedConnector Dsub15pinPlug XM2A 1501 madebyOMRONCorp RecommendedCover Dsub15pinCover XM2S 1511 madebyOMRONCorp JackScrew XM2Z 0071 madebyOMRONCorp Use rough metric type M2 6 x 0 45p threads used to hold the ...

Страница 8: ...asteners with a screwdriver To create a waterproof seal a force of 0 5 0 6N m is required Panel GLC unit Tightening the screws with too much force can damage the GLC Before installing the GLC be sure that the moisture resistant gasket is attached securely to the unit 6 Installation Rear of GLC Gasket 1 6mmto10mm Panelthickness 302 under 4 R2 228 Unit mm 0 1 0 1 ...

Страница 9: ...ill result in excess noise and vibration Wherever possible use thick wires max 2 mm2 for power terminals and twist the wire ends before attaching the ring terminals Be sure to use the following size Ring Terminals 7 Wiring Under 6 0mm Over φ 3 2 mm WARNING 1 Ring Terminal to use V2 MS3 made by JST Rear side FG FG Ring Terminals 1 Power Input Terminal Block Connect the power cable following the ste...

Страница 10: ...in circuit lines high voltage high current or input output signal lines Connect a surge absorber to deal with power surges To reduce noise make the power cable as short as possible 8 Precautions for Supplying Power 11 Replacing the Backlight 10 Precautions for Input Output Signal Lines Input and Output signal lines must be separated from the power control cables for op erational circuits if this i...

Отзывы: