The GLC300-TC41-24V are UL / c-UL recognized products. (UL file No.E182139)
■
GLC conforms as a component to the following standards:
・
UL508
Industrial Control Equipment
・
UL1604
Electrical Equipment for Use in Class
Ⅰ
and
Ⅱ
Division 2 and Class
Ⅲ
Hazardous (Classified) Locations
・
CAN/CSA-C22.2, Nos.142, and 213-M1987
Standard for Safety of Information Technology Equipment, including
Electrical Business Equipment
GLC300-TC41-24V(UL Registration Model : 2780027-02)
・
The GLC should be installed in the front face of a metal panel.
・
If the GLC is installed so as to cool itself naturally, be sure to install it in a verti-
cal panel. Also, be sure that the GLC is mounted at least 100mm away from
adjacent structures and other equipment, otherwise, the heat generated by the
GLC's internal components may become higher than that allowed by UL stan-
dard requirements.
Installation and operation instructions are provided with each GLC. These installa-
tion instructions contain the following statements.
1. Power, input and output (I/O) wiring must all be in accordance with Class I, Division
2 wiring methods, Article 501-4 (b) of the National Electrical Code, NFPA 70, or as
specified in Section 18-152 of the Canadian Electrical Code for units installed within
Canada, and in accordance with that location's authority.
2. Suitable for use in Class I, Division2, GroupsA, B, C and D hazardous location, or
nonhazardous locations only.
3. WARNING: Explosion hazard-substitution of components may impair suitability for
Class I, Division2.
4. WARNING: Explosion hazard-do not disconnect equipment unless power has been
switched off or the area is known to be nonhazardous.
5. WARNING: Explosion hazard-when in hazardous locations, turn off power before
replacing or wiring modules.
UL / c-UL (CSA)Approval
CE Marking
GLC300-TC41-24V are CE marked , EMC compliant products.These units also
conform to EN50081-2 , EN50082-2 directives.