1
Recommended Ring Terminals: V2-MS3 (made by JST)
Use the following steps when connecting the Ring Terminals.
1. Confirm that the Power Cord is unlugged from the power supply.
2. Remove the Power Input Terminal Block's plastic cover.
3. Remove the screws from the 3 terminals to be used and align the terminals.
Then, re-insert the screws and tighten them in place.
(Be sure the wires are correctly connected)
• The torque necessary for tightening the screws is from 0.5 - 0.6
N•m.
• To avoid the possibility of an electric shock, be sure the Power Cord is
unplugged from the power outlet prior to connecting the power cord's power
terminals to the GLC.
• The GLC100-LG41-24V and GLC100-SC41-24V can only use DC24V in-
put. Any other input voltage can damage the GLC and its power supply.
• Since the GLC has no power switch, be sure to use a breaker type switch.
• To prevent a short from occurring when the ring terminals
become loose, be sure to use sleeved ring terminals.
Ring Terminals*
1
+ - FG
+
-
FG
Rear of GLC
Power Input
Terminal Block
When the FG terminal is connected, be sure the wire is
grounded. Not grounding the GLC unit will result in excess
noise and vibration.
• Wherever possible, use thick wires (max. 2 mm
2
) for power
terminals, and twist the wire ends before attaching the ring ter-
minals.
• Be sure to use the following size Ring Terminals.
5
Wiring
Under
6.0 mm
Over
φ
3.2 mm
WARNING