Recommended Ring Terminals: V2-MS3 (made by JST)

Use the following steps when connecting the Ring Terminals.

1. Confirm that the Power Cord is unlugged from the power supply.

2. Remove the Power Input Terminal Block's plastic cover.

3. Remove the screws from the 3 terminals to be used and align the terminals.

Then, re-insert the screws and tighten them in place.

(Be sure the wires are correctly connected)

  The torque necessary for tightening the screws is from 0.5 - 0.6

Nm.

• To avoid the possibility of an electric shock, be sure the Power Cord is

unplugged from the power outlet prior to connecting the power cord's power
terminals to the GLC.

• The GLC100-LG41-24V and GLC100-SC41-24V can only use  DC24V in-

put.  Any other input voltage can damage the GLC and its power supply.

• Since the GLC has no power switch, be sure to use a breaker type switch.

 To prevent a short from occurring when the ring terminals
   become loose, be sure to use sleeved ring terminals.

Ring Terminals*

1

+    -    FG

+

-

FG

Rear of GLC

Power Input
Terminal  Block

When the FG terminal is connected, be sure the wire is
grounded.  Not grounding the GLC unit will result in excess
noise and vibration.
•  Wherever possible, use thick wires (max. 2 mm

2

) for power

   terminals, and twist the wire ends before attaching the ring ter-

minals.

  Be sure to use the following size Ring Terminals.

5

Wiring

Under

6.0 mm

Over 

φ

 

3.2 mm

 WARNING

Содержание GLC100-LG41-24V

Страница 1: ... GLC If the GLC s internal program enters RUN mode prior to the I O unit s load control power turning ON an incorrect output signal or malfunction could cause an accident to occur Design a user program that will ensure the safety of the user s system in the event of a GLC display or control error or in the event of either a data transmission error or power failure between the GLC and a connected u...

Страница 2: ...e damaged if it falls off the back of the GLC or a system related malfunction or accident may occur due to I O data signal problems Be sure any data cable attached to the GLC s connector is securely attached If the cable and connector pins do not all make complete contact incorrect input or output signals can result General Wiring Cautions To prevent shocks or malfunctions GLC s FG earth wire shou...

Страница 3: ...owed by UL standard requirements Installation and operation instructions are provided with each GLC These installation instructions contain the following statements 1 Power input and output I O wiring must all be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 or as specified in Section 18 152 of the Canadian Electrical Code for units in...

Страница 4: ...ease contact your local GLC distributor immediately Package Contents User s Manual Sold Separately GLC100 User s Manual GLC Option Items Logic Program Development soft ware Sold Separately Pro Control Editor GLC Unit GLC100 LG41 24V GLC100 SC41 24V Operation Instructions 1 this sheet Installation fasteners 4 pcs Operation Instructions Digital GLC100 MU41 Japanese Version Only Digital GLC100 User s...

Страница 5: ...upply D Power Input Terminal Block Provides power input and grounding termi nals for GLC s AC power cord E Expansion Interface Used for connecting expansion units to the GLC F Serial Interface RS 232C RS 422 Serial interface Con nects the GLC to the Host G Tool Connector Connects the Screen Data Downloading Cable or Bar Code Reader to the GLC A B C 1 Names and Functions of GLC Parts The GLC100 LG4...

Страница 6: ... 232C connections Do not connect 9 TRMX 10 RDA 11 SDA 15 SDB 16 RDB 18 CSB 19 ERB 21 CSA and 22 ERA Pin Signal Name Condition Pin Signal Name Condition 1 FG Frame ground 14 VCC 5V 5 output 0 25A 2 SD Send data RS 232C 15 SDB Send data B RS 422 3 RD Receive data RS 232C 16 RDB Receive data B RS 422 4 RS Request send RS 232C 17 NC No connection 5 CS Clear send RS 232C 18 CSB Clear send B RS 422 6 NC...

Страница 7: ...C 156 123 5 Rear of GLC Gasket Before installing the GLC be sure that the moisture resistant gasket is attached securely to the unit 4 Installation Be sure to connect this unit s SG GND Signal Ground terminal to the other unit s Signal Ground terminal If necessary you may also need to connect the FG terminal to the other unit s FG ter minal depending on the type of the other unit you use This unit...

Страница 8: ...o connecting the power cord s power terminals to the GLC The GLC100 LG41 24V and GLC100 SC41 24V can only use DC24V in put Any other input voltage can damage the GLC and its power supply Since the GLC has no power switch be sure to use a breaker type switch To prevent a short from occurring when the ring terminals become loose be sure to use sleeved ring terminals Ring Terminals 1 FG FG Rear of GL...

Страница 9: ...roper Backlight for your specific GLC 100 model When attaching an option unit to the GLC be sure to follow the option unit s operation instructions GLC Backlight Model GLC100 LG GLC100 SC GP370 BL00 MS When changing the backlight be sure to wear gloves and use the fol lowing steps 1 Unplug the GLC s power cord from the power supply 2 Detach the power cord from the GLC A 3 With a screwdriver unfast...

Страница 10: ...hment screws G When reconnecting the GLC s covers be careful not to pinch any of the backlight wiring between the covers 6 Push the connector clip to the right and pull out the backlight F Do not move the clip to the left when removing the back light since it may break off Power Cord B C Connector A D Internal Pad G F Clip Backlight Connector E Positioning Tabs Center Attachment Screws Hole ...

Отзывы: