PWP Wind Control Panel Manual 2 -ARAC-103 

 

 

 

 

Wind Generator Connection Diagram  

12/24 VDC House Battery 

 

Wind Control Panel Connection Diagram 

 

 

 

 
 

 
 

 

Wind 

Generator 

 

 

 
 

 

 
 

Battery 

Bank 

     

Battery to Fuse  

connection max of 7"   

       per ABYC Fuse (optional) 

+

 

 

-

 

 

   

RED 

BLACK 

 

 

 

Mechanically support 
wires in mast from 
pulling on splices. 

 

 

 

Notes: 

1) 

Wire size is critical to the successful operation of the alternat ive 
energy system.  If greater wire lengths are needed, wire size 
may have to be changed and sized to allow a maximum of 3% 
voltage drop over the distance of the connection. 

2) 

Locate the 

Wind Control Panel (WCP

) in an area close to the 

 
 

 

_

 

 

 1      2       3       4

house battery bank but outside any high temperature areas. 
Do 
not install in a tight battery compartment that houses vented 
wet cell batteries.  Must be in a dry compartment. 

3) 

Do not run wind generator wires in bundles that contain SSB 
radio antenna. 

4) 

Always place STOP-RUN switch on the WCP in STOP position 
prior to making connections to the WCP. 

5) 

Battery connection is made last.  Wind Circuit Breaker on the 
WCP must be placed in the OFF position prior to making final 
connections at the battery. 

6) 

Crimp and butt splice connections are critical for proper system 
operation.  Use proper crimping tools and complete clean, 
stripped wires when making these connections. 

7) 

Wind generator is required to have a built in regulator (e.g. AIR 
Wind Turbines) to prevent overcharging of batteries.  If wind 
generator is not equipped with a built-in-regulator, an external 
shunt regulator (a diversion load controller) or similar should 
be connected to the battery to prevent    overcharging 
condition by the wind generator. 

 

    Wind

 

Generator

 

Battery

 

Содержание 2-ARAC-103

Страница 1: ...In the RUN position it allows the wind turbine to operate and produce power while in the STOP position it places an electric brake on the wind turbine spindle stopping the rotation in this mode slight blade rotation may occur in strong winds The center position is an OFF position disconnecting the wind turbine but is not recommended The Ammeter monitors the wind turbines production The wind contro...

Страница 2: ...the terminal block TB 3 Using the template cut the large opening and drill the six mounting holes ELECTRICAL INSTALLATION 1 Wind Turbine Connect the wires of the wind turbine TB 3 Negative Black to Terminal 2 and Positive Red to Terminal 1 of the Control Panel using the appropriate wire size and crimps The Green Ground wire of the wind turbine should not be connected to the boat grounding system b...

Страница 3: ...TOP position Connect the battery feed wires from the Control Panel to the battery bank terminals Make sure all connections are tight and the wires are properly sized TROUBLESHOOTING 1 Wind Turbine is Cycling On Off When the battery bank is approaching full charge the wind turbine may start and stop frequently This is caused by the wind turbine attempting to do the final top off on to your battery ...

Страница 4: ...ving the circuit breaker on and wind circuits active will deplete only a minor amount of energy from your battery during non energy producing periods and should not be of concern The wind system works in harmony together with other energy producing systems on board such as solar PV alternator or AC powered battery charger and therefore it is not necessary to turn off the wind circuit breaker when ...

Страница 5: ... a tight battery compartment that houses vented wet cell batteries Must be in a dry compartment 3 Do not run wind generator wires in bundles that contain SSB radio antenna 4 Always place STOP RUNswitch on the WCP in STOP position prior to making connectionsto the WCP 5 Battery connectionis made last Wind Circuit Breaker on the WCP must be placed in the OFF position prior to making final connection...

Страница 6: ...Lakewood CO 80215 primuswindpower com Pg 5 5 PWP Wind Control Panel Manual 2 ARAC 103 Appendix Wind Control Panel 1 1 Cutout Cut along dotted line Drill 6 Holes 3 16 inch 938 Quail Street ...

Отзывы: