PWP Wind Control Panel Manual 2 -ARAC-103
Wind Generator Connection Diagram
12/24 VDC House Battery
Wind Control Panel Connection Diagram
Wind
Generator
Battery
Bank
Battery to Fuse
connection max of 7"
per ABYC Fuse (optional)
+
-
RED
BLACK
Mechanically support
wires in mast from
pulling on splices.
Notes:
1)
Wire size is critical to the successful operation of the alternat ive
energy system. If greater wire lengths are needed, wire size
may have to be changed and sized to allow a maximum of 3%
voltage drop over the distance of the connection.
2)
Locate the
Wind Control Panel (WCP
) in an area close to the
+
_
+
_
1 2 3 4
house battery bank but outside any high temperature areas.
Do
not install in a tight battery compartment that houses vented
wet cell batteries. Must be in a dry compartment.
3)
Do not run wind generator wires in bundles that contain SSB
radio antenna.
4)
Always place STOP-RUN switch on the WCP in STOP position
prior to making connections to the WCP.
5)
Battery connection is made last. Wind Circuit Breaker on the
WCP must be placed in the OFF position prior to making final
connections at the battery.
6)
Crimp and butt splice connections are critical for proper system
operation. Use proper crimping tools and complete clean,
stripped wires when making these connections.
7)
Wind generator is required to have a built in regulator (e.g. AIR
Wind Turbines) to prevent overcharging of batteries. If wind
generator is not equipped with a built-in-regulator, an external
shunt regulator (a diversion load controller) or similar should
be connected to the battery to prevent overcharging
condition by the wind generator.
Wind
Generator
Battery