Timer Switch Control Installation
Classic Series Digital Elapsed Timers and Code Blue Timers include a Timer Switch Control that controls the timer functions.
Installation requirements
(1) Timer Switch Control (supplied)
(1) Connector cable (supplied). Cable is a standard 15 ft. (4.6 meter) CAT5 network cable with an RJ-45 connector The cable length
can be extended up to 100 ft. (30.4 meter). Required to connect timer control switch to timer unit.
(1) Single-gang junction box (not supplied). Recommend use of a 2¼ in x 2¾ in. x 4 in. (5.72 cm x 6.99 cm x 10.16 cm) junction
box.
How to install a Timer Switch Control
1. Wire the code blue timer input to the code blue system.
For a code blue system that applies a voltage to start a code blue event: wire the timer 4 pin connectors RED (Positive Code
Blue Input) and BLACK (Negative Code Blue Input) wires to the code blue system. An input voltage of 5-120V (AC or DC) can
be used. When using DC, be sure to use the correct polarity; RED wire is positive and the BLACK wire is ground. Code Blue
start and stop events are triggered by the application of voltage across the code blue input wires.
2. Connect the timer control switch to the timer using the supplied cable.
3. Securely mount the timer control switch into a single-gang junction box.
NOTE
Timer control switch membrane and wall plate may be cleaned with water or most common disinfectants. Be sure to test
any cleaning solutions on a small area.
Timer Switch Control wiring specifications