10 CW6CDC Level Controller User Manual
CONFIGURATION
To enter the configuration mode, simultaneously press the
LEFT and RIGHT
arrow key and hold for three (3) seconds with the unit powered
ON
.
NOTE:
Eight (8) seconds of inactivity (no keys pressed) will terminate the
configuration menu and exit back to the run menu.
The first item in the configuration menu is the
UNITS
selection. Use the
LEFT or
RIGHT
arrow keys to navigate through all the items in this menu.
UNITS
Select the unit of measure display after the process value.
FT
= Feet
IN
= Inches
CM
= Centimeters
%
= Percentage
oC
= Degrees Celsius
oF
= Degrees Fahrenheit
PS
= Pound Per Square Inch (PSI)
BR
= Bar
NONE
= Blank, No Units Displayed
When you are at the item you wish to edit, press the
ENTER
key and the original
value for the item selected will flash. Use the
UP
and
DOWN
arrow keys to change
to your desired value and press
ENTER
.
NOTE:
The edited value will not be saved until the
ENTER
key is pressed.
4 mA
Set the value displayed when the signal value is equal to 4 mA (zero).
The default value is zero.
20 mA
Set the value displayed when the signal value is equal to 20 mA (span).
The default value is 10.0.
BAR MIN
This value set the level for which all bars on the bar graph will turn OFF.
BAR MAX
This value set the level for which all bars on the bar graph will turn ON.
OFFSET
An offset value can be added or subtracted to bring the display value to
zero at atmospheric pressure. If you are using a submersible pressure transducer,
the level readout at atmospheric pressure (out of the wet well) should be zero. If it
is not, add or subtract (negative) a value to bring the display to zero. Check the
level readout to verify it is zero. If not, try changing the offset again.