9 CW6CDC Level Controller User Manual
LEVEL DISPLAY
The adjustable
ON and OFF
function allows for an individual hysteresis or
differential setting of each set-point. For an
emptying
application, the
ON
set-
point must be
greater
than the
OFF
set-point. For a
filling
application, the
ON
set-point must be
less
than the
OFF
set-point
(Refer to
FIGUIRE 5
).
NOTE: For proper operation of the CW6CDC controller, the ON and OFF
set-points must not be set to the same value.
FIGURE 5