Probe Installation 

 
Mount the probe so that the metal passes between the probe face and the magnetic 
source (conveyor).   We recommend the initial probe gap to conveyor belt should be 
12mm (.5”) or less.  Do not hard mount the probe bracket at this time. With no metal 
present the probe must detect at least 100 gauss from the magnetic conveyor.  It is wise 
to leave the probe mounting loose until the ideal location is determined using the 

Meter 

Mode

 feature cover on page 5. 

 
The Models DS71 and DS72 with the Model PN18 Single probe Double Sheet Detector 
can operate without the probe touching the target metal.  It uses the residual magnetic 
field that attracts the metal to the conveyor.  The magnet acts like a transmitter in a dual 
probe detector. The Magnetic field will permeate through the metal blank.   The 
thickness of a non metallic belt will not adversely affect the magnetic strength as long as 
it is blank is held closely to the belt surface. The unit must be calibrated after the gap is 
established.  If the gap is too large, the unit will not calibrate.  Use the meter mode 
(page 5) to determine the maximum gap. 
 

We recommend you always locate the sensor to achieve maximum coverage of the target metal 
blank when calibrating.  Calibration at a location where the maximum field is not blocked may 
cause false doubles.  During production the metal may move to a point where more flux is 
covered.  This is especially true when the shape of the blank varies. Typically the blank should 
cover the magnetic to the PN18 for approximately 50 mm (2”).  If the target is smaller than 
50mm, then locate it where the maximum coverage is located using the meter mode.  Calibrate at 
that position. 

 

 
Electrical Wiring 

 
The connection between the probe and the controller requires a Prime Controls adapter 
cable model CBL110-2.  The cable has a connector at either end and does not require 
external wiring.  Probe and control separation should be within the 2 meter cable length. 
 
Power to the controller and the outputs connect through an industrial standard male, 
four-pin, 12mm connector.  For noise immune connection use Prime Controls specified 
Model CBL104-3 cable. 
 
The CBL104-3 pin-out is as follows and the connected individual wire colors: 
 
 

 

Pin 1  - 

Power  

 

Brown wire on standard cable 

 

 

Pin 2  - 

Single Output 

White wire on standard cable 

 

 

Pin 3  - 

Common 

 

Blue wire on standard cable 

  Pin 

- No-double 

Output  Black wire on standard cable 

 
Cable shields should not be strip from wires more than 50mm or 2 inches to maintain 
noise immunity.  Route the cables away from any high power wiring and machinery to 
maintain noise immunity.  Make sure the Pin 3 Common (blue) is uninterrupted to the 
common of the source power supply. 

Содержание FLUXIMITY DS71

Страница 1: ...ers are explained is this instruction sheet The Fluximity system includes a microcontroller based control module in a 18mm threaded aluminum housing The Controller is connected to a family of magnetic...

Страница 2: ...ule Installation The DS71 72 Controller module is designed to mount with a simple bracket where convenient between the probe and a higher level controller such as a PLC Avoid mounting locations with e...

Страница 3: ...t a location where the maximum field is not blocked may cause false doubles During production the metal may move to a point where more flux is covered This is especially true when the shape of the bla...

Страница 4: ...rmal indicator colors are covered on page 8 If the magnetic field signal is strong the multi function indicator will be off this assumes the probe face was mounted within 50mm of the magnetic conveyor...

Страница 5: ...ignal The Fluximity operates best if the magnetic strength is 100 gauss Gauss G is a unit of measurement for magnetic field strength or flux density For example approx 1 gauss from earth s magnetic no...

Страница 6: ...econds elapses with no press of the pushbutton The detector has a standby calibration feature that permits calibration while the metal is moving Press the pushbutton once with no metal between the mag...

Страница 7: ...thickness of the two samples is too close for reliable gauging the indicator flashes amber at a 10 Hz rate for up to 15 seconds or until the pushbutton is pressed again After 15 seconds it returns to...

Страница 8: ...ber and then begins flashing red rapidly 10 Hz This can indicate a there is metal present b the probe is disconnected or c the cable to the probe has an open or d the probe is faulty During Single Hit...

Страница 9: ...FIRMWARE VERSION The format of the firmware version number is of the form 1 2 comprising a single digit integer part and a single digit fractional part When first powered up the controller displays t...

Страница 10: ...ection 12 mm Connector Pin 4 Max source current 50mA fuse limited Output Voltage High Supply Voltage less 1 volt Over current protection Self resetting thermal fuse ESD protection Transient Voltage Su...

Страница 11: ...11 DS71 DRIVE CIRCUITRY CONTROLLER 30V 30V 30V 2 1 4 3 50 mA 50 mA V COM SINGLE NO DOUBLE DS72 DRIVE CIRCUITRY CONTROLLER 30V 30V 30V 2 1 4 3 50 mA 50 mA V COM SINGLE NO DOUBLE...

Страница 12: ...F ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR PURPOSE THE LIABILITY OF PRIME CONTROLS TO ANY PURCHASER SHAL...

Отзывы: