background image

24

UnderfLoor ModUfLex ControLLer - Manual 

  |   

priceindustries.com

Underfloor ModUflex Controller

MAINTENANCE

Fault

Solution

Controller appears to be not 
responding or have no power. 
Green light on the controller is 
not blinking. Thermostat green 
indication light not on, or LCD 
screen is blank.

Check thermostat first for either green indication light, or LCD display. If either of these does not appear, 
then check the controller for power (green blinking light). If no power is present, check 24VAC power with 
a multimeter. Cycle power to the controller. If this doesn’t restore power, check the power that is feeding 
that controller for your problem.

Dampers don’t move, and red 
FAULT light is illuminated. 

Red fault light means there is a short in the cable from CW/CCW to COM. Find shorted cable(s) in that 
string of dampers and replace.

Damper acts erratically

If the CW/CCW lines in the cable are shorted together (and not shorted to the COMMON), it could cause 
the dampers in a string to act erratically and drive in random directions.
Find bad cable(s) in the string, and replace.

24 VAC Binary Outputs not 
functioning

Ensure that the controller has 24VAC power. 

Ensure that there is a call for heating or for cooling, room lights, etc. If so, check to see that the GREEN 
indication light is on for the output.   

The next step would be to check the device that is triggering the output like a relay. Ensure that the relay 
has engaged (pulled in) for either heating or cooling application. 

Check the output configuration

Analog Outputs not functioning

Ensure that the UMC3 has 24VAC power. Check the analog output for voltage with a multimeter. You 
should see a voltage in the range of 0-10VDC.

Direct Acting Output – 0VDC indicates that the field device is closed or at a minimum position. 10VDC 
indicates that the field device is open or at a full open position. Direct Acting is typical with cooling 
applications.

Reverse Acting Output – 0VDC indicates that the field device is fully opened or maximum position, and 
10VDC indicates fully closed or minimum position. Reverse acting is typical with heating applications.

SAT Sensor Analog Input not 
functioning

Ensure that there is a sensor wired to the input on the UMC3 controller. Check the type of sensor, should 
be a 10k Ohm Type Thermistor.

BACnet Communication Errors

BACnet - MS/TP is based on a RS-485 network. It must be wired in a daisy chain configuration. A daisy 
chain means that there is only one main cable, and every network device is connected directly along its 
path.  

DO NOT use Star, Bus, “T”, or any other type of network configuration. Any of these other network 
configurations will result in an unreliable network, and make troubleshooting almost impossible.  

Correct polarity is imperative on MSTP wiring. Always ensure that the positive terminal on a device has 
the same color wire connected to it throughout the network, same for the negative terminal. Eg. 2 wire 
conductor with black and white wires – black to the positive terminal, and white to the negative terminal. 
Keep this consistency throughout the network.

troubleshooting

The following information is provided in the event that the UMC3 does not appear to function properly after installation.

Содержание UMC3 Series

Страница 1: ...MANUAL INSTALLATION SERVICE Underfloor ModuFlex Controller UMC3 Series v100 Issue Date 09 20 17 2017 Price Industries Limited All rights reserved...

Страница 2: ...e Flow Response Chart 5 Input Output Description 6 Wiring 7 Thermostat Installation 8 How to use Thermostats 9 Display Navigation Initial Startup 10 Service Menu 11 Balancing Menu 12 VVT Menu 13 Setpo...

Страница 3: ...with the necessary precautions Individuals may be exposed to certain components or conditions such as refrigerants oils materials under pressure rotating components and both high and low voltage durin...

Страница 4: ...use of a variable volume basket The variable volume diffusers would be controlled by the UMC The UMC would open and close the diffusers releasing air from the pressurized plenum The variable volume VA...

Страница 5: ...he controller and thermostat is simple and error proof with RJ 45 network type connections to the thermostat and BACnet network The UMC3 comes factory mounted in a rugged galvanized enclosure complete...

Страница 6: ...ted openings for modular cable connections Temperature sensor input for monitoring Disconnect switch Pluggable 24VAC power terminal Operation The UMC3 controller is an advanced and fully configurable...

Страница 7: ...t HCCO Response Cooling Min Cooling Flows Heating Min Heating Flows Neutral Supply Air Flow PI Cooling Supply air Cold D L PI Heating Supply air Cold D L PI Neutral Supply air Cold D L PI Cooling Supp...

Страница 8: ...from a third party thermostat In this configuration AI4 is the 0 10VDC cooling load input Can also be used for simple voltage monitoring when analog inputs are not configured as control source AI5 Hea...

Страница 9: ...7 priceindustries com Underfloor ModuFlex Controller Manual Underfloor ModuFlex Controller INSTALLATION MOUNTING INSTRUCTIONS Wiring Below is an example of a typical UMC3 layout...

Страница 10: ...o a standard electrical box or directly to drywall using anchors supplied by others 2 Run the CAT 5 cable through the center hole in the plate and connect the cable to the thermostat Then secure the t...

Страница 11: ...s in One blink is cooling mode two blinks is heating mode three blinks is neutral Wireless Thermostat Functionally identical to the Dial Thermostat Requires wireless receiver see Wireless Thermostat m...

Страница 12: ...point adjustment PRICE ELECTRONICS Start up screen LCD THERMOSTAT STANDARD MODEL Standard Motion Model LCD THERMOSTAT VERSION X XX Displays firmware version of thermostat LOADING INITIALIZING Loading...

Страница 13: ...e damper open close min max VVT Allows you to set limits in VVT mode SETPOINT Setup of Setpoint limits day minimum maximum F C selection INPUT Shows thermistor reading Allows setting of HCCO if desire...

Страница 14: ...MAX Cool Max Regular and LFGH dampers go to their Cool Maximum positions DPR OVERIDE GOTO HEAT MIN Heat Min Regular and LFGH dampers go to their Heat Minimum positions DPR OVERIDE GOTO HEAT MAX Heat...

Страница 15: ...eat Maximum Position in Range 0 100 Default Depends on sequence LFGH NEUTRAL 0 LFGH Neutral Supply Air position not normally used LFGH position in when Neutral supply air is present Range 0 100 Defaul...

Страница 16: ...t 83 0 F PRO BAND 2 0 F Proportional Band The Proportional Band is the temperature range through which the controller calculates a 0 100 load Range 0 5 F 25 0 F Default 2 F DAY DIFF 1 0 F Day Differen...

Страница 17: ...ded Neutral Mode Force Cool UMC3 Default Controller assumes cold supply air at all times despite any reading of T1 Thermistor input This is useful by allowing the T1 thermistor input to be used for mo...

Страница 18: ...ng and the heat load is at or above trip point below USED AS COOL OUTPUT Output energized when the room demand is cooling and the cool load is at or above trip point USED AS HEAT AND COOL Output energ...

Страница 19: ...for cooling Default 0 0VDC AUX COOL MAX 10 0 VDC Auxillary Cool Max Voltage Outputs this voltage on Auxiliary Analog pin when there is a maximum call for cooling Default 10 0VDC AUX HEAT MIN 0 0 VDC...

Страница 20: ...sensitive 5 DEFAULT Only visible when motion is enabled MOTION TEST OFF Motion Test Motion sensor STAT only Motion Thermostat will beep each time motion is sensed This is useful for adjusting the sen...

Страница 21: ...POS 50 Damper Position This indicates the current position of the damper in percent Range is 0 100 100 full open or maximum air DAMPER TARGET 50 Damper Target This indicates the current target of the...

Страница 22: ...n your building site Range 1 4 194 303 NOTE After changing Device Instance the thermostat will send a RESET command to the UMC3 to apply the ADDRESS changes Addresses are only READ on startup so after...

Страница 23: ...This option of setting the Address through the software is available when the controller is not accessible to the user finished drywall ceiling for example PC OR ROUTER PC OR ROUTER Device Instance D...

Страница 24: ...NKER Tool Below is a table defining how a Device Instance number is obtained NOTE Each device on a network segment must be set to run at the same speed or baud rate Example Device Instance setup with...

Страница 25: ...ack of the thermostat via an RJ 12 cable supplied by Price Setup of the controller can then be performed using the connected laptop LAPTOP CONNECTION An LCD Thermostat can be purchased as an upgrade a...

Страница 26: ...uration Analog Outputs not functioning Ensure that the UMC3 has 24VAC power Check the analog output for voltage with a multimeter You should see a voltage in the range of 0 10VDC Direct Acting Output...

Страница 27: ...from voltage spikes The most practical method of grounding is to ground every 24VAC transformer common neutral used to power the controls Connect the common neutral wire of the SECONDARY side of the t...

Страница 28: ...s document contains the most current product information as of this printing For the most up to date product information please go to priceindustries com 2017 Price Industries Limited All rights reser...

Отзывы: