background image

..\Manuals\RCI-200-SER 

                                                                                                          Page 5 of 12 

SERIAL Communication Option: 

 
The -SER communications option for the RCI series utilizes either an RS-232 or RS-485 link to 
exchange the signal data between a host and its remote(s).  There are three types of 

Topologies

 that 

can be configured: 1) Point-to-Point, 2) Host-to-Multipoint and 3) PC-to-Multipoint 
 
In a 

Point-to-Point

 topology one 

host communicates with one remote.  
The two exchange all their signals 
with one another. The remote is 
configured as remote #1 even 
though it is the only remote in the 
system. 
 
 
In a 

Host-to-Multipoint

 topology 

one host communicates to several 
remotes. Each remote is assigned 
an address (1,2,3, etc.) so that the 
host may distinguish between them.  
There may at most be as many 
remotes as there are inputs & 
outputs on the host.   
 
For example, an RCI-200 system, 
having two analog/contact inputs 
and outputs, may communicate with 
up to two remotes each having one analog/contact input and output.  In this case all 

#1 inputs and 

outputs on the host correspond to the #1 inputs and outputs on remote #1

 and all 

#2 inputs and 

outputs on the host correspond to the #1 inputs and outputs on remote #2

.  

 
 
In a 

PC-to-Multipoint

 topology one 

PC (or PLC) host communicates 
with one or more remotes via 
MODBUS ASCII protocol.  Software 
that runs on the PC (or PLC) takes 
the place of the Host and can 
directly read and write the inputs and 
outputs of the remote units. Each 
remote is assigned an address 
(1,2,3, etc.) so that the host may 
distinguish between them.   

Содержание RCI-200 series

Страница 1: ...00 XXX If special or required 24 VDC 2 Dry Contacts and 2 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 2 Form C Contacts and 2 Analog Outputs 117VAC 50 60Hz XXX RF9 90...

Страница 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Страница 3: ...cks make for easy installation When connecting units on a PBX system make sure it can accept analog modem transmissions Serial systems connect via standard modem cable Standard Features Bi directional...

Страница 4: ...ter 232 485COM RS 232 RS 485 up to 128 devices RS 485 Bus R S 232 System A System B System C Additional Signal Booster s required for 32 devices see SPB 485 Manufactured By 11 25 9 25 4 5 www pribusin...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...0mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 200 to 240VAC power make sure to change the f...

Страница 9: ...ts are connected to the RCI 200 in two fashions 1 Normal 3 wire connection or 2 two wire connection On a 3 wire connected input an external power supply or the 24V power output terminal of the RCI pro...

Страница 10: ...om the inputs Care must be taken when connecting the outputs to different devices so that no inadvertent ground loops are established Output Calibration Input Testing The outputs on the RCI 200 are fa...

Страница 11: ...nications failure occurs If H1 3 IN then analog output 1 will ramp to the setting of K1 and analog output 2 will ramp to the setting of K2 Both outputs will change at a rate determined by the setting...

Страница 12: ...ddress 1 2 3 etc so that the host may distinguish between them There may at most be as many remotes as there are inputs outputs on the host For example an RCI 200 system having two analog contact inpu...

Страница 13: ...perate as a host unit make sure that SW2 8 is flipped down Next set the number of remotes that the host is to communicate with using SW1 1 2 3 These switches are binary encoded as shown in the chart t...

Страница 14: ...e to convert the remote address to binary first SW1 1 SW1 2 SW1 3 Remote Address UP UP UP 1 DOWN UP UP 2 UP DOWN UP 3 DOWN DOWN UP 4 UP UP DOWN 5 DOWN UP DOWN 6 UP DOWN DOWN 7 DOWN DOWN DOWN 8 Next se...

Страница 15: ...2 Next set the number of channels on this remote using SW2 1 2 One channel is considered 1 analog input output plus 1 contact input output Hence an RCI 200 can have at most 1 channel SW2 1 SW2 2 Chann...

Страница 16: ...sters listed in the table below are the only ones implemented on all RCI products at this time Description Function RCI 100 XXX RCI 200 XXX RCI 400 XXX RCI 800 XXX Read Relay Status 01 00001 00001 000...

Страница 17: ...2 Number of Remotes 1 Address 1 Channels on Remotes 2 Example 3 An RCI 400 Host communicating with an RCI 400 Remote RCI 400 Host RCI 400 Remote Host Channels 4 Remote Channels 4 Number of Remotes 1 A...

Страница 18: ...ample 4 An RCI 800 Host communicating with 3 RCI 200 Remotes RCI 200 Host RCI 100 Remote 1 RCI 100 Remote 2 Host Channels 2 Number of Remotes 2 Channels on Remotes 1 Remote Channels 1 Address 1 Remote...

Страница 19: ...Page 12 of 12 RCI 800 Host Host Channels 8 Number of Remotes 3 Channels on Remotes 2 RCI 200 Remote 1 RCI 200 Remote 2 RCI 200 Remote 3 Remote Channels 2 Address 1 Remote Channels 2 Address 2 Remote...

Отзывы: